FIR01-00570
| INSP-Final Inspection | 12/6/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | A | PASS |
|
|
Fire sprinkler system finaled 12/7/2001 1:24:40 PM
|
FIR01-00589
| INSP-Final Inspection | 12/6/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | A | CANC |
|
|
duplicate inspection 12/7/2001 10:41:40 AM
|
BLD01-00265
| FIRE-Final Inspection | 12/6/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | A | FAIL |
|
|
Emergency lights and exit signs would not operate. Inspection to be rescheduled 12/7/2001 8:29:56 AM
|
BLD01-02719
| FIRE-Final Inspection | 12/7/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 12/7/2001 10:38:41 AM Fire life/safety finaled. Fire sprinkler finaled. Fire alarm given temp.
|
FIR01-00592
| INSP-Final Inspection | 12/7/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | A | PART |
|
|
Added by Inspector: 430 On 12/7/2001 10:40:58 AM SIgned temp per Sam Rogers. Sprinkler monitoring and duct shutdown on three units operating correctly. Inspection to be scheduled to test all other devices when operational.
|
FIR01-00401
| INSP-Final Inspection | 12/7/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 430 On 12/7/2001 3:35:45 PM Provide tamper switches on control valves in riser room, provide tamper switch on dry pipe alarm trim, provide "Fire Sprinkler Room" sign on riser room, hard wire the air compressor, provide lock on fire alarm panel circuit, provide "knox box", provide map in knox box and at facp, provide low air pressure switch, verify single pressure switch is ok for two dry pipe risers, test exterior bell and sign
|
FIR01-00317
| INSP-Sprinkler Rough-in | 12/7/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | P | PART |
|
|
Holding cells and restrooms ok to cover 12/7/2001 4:00:27 PM
|
FIR01-00589
| INSP-Final Inspection | 12/6/2001 | 12/7/2001 | 12/7/2001 12:00:00 AM | P | PASS |
|
|
Fire alarm system finaled 12/7/2001 10:36:47 AM
|