Inspections for the day of: Friday, December 7, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00570 INSP-Final Inspection12/6/200112/7/200112/7/2001 12:00:00 AMAPASS
Fire sprinkler system finaled 12/7/2001 1:24:40 PM
FIR01-00589 INSP-Final Inspection12/6/200112/7/200112/7/2001 12:00:00 AMACANC
duplicate inspection 12/7/2001 10:41:40 AM
BLD01-00265 FIRE-Final Inspection12/6/200112/7/200112/7/2001 12:00:00 AMAFAIL
Emergency lights and exit signs would not operate. Inspection to be rescheduled 12/7/2001 8:29:56 AM
BLD01-02719 FIRE-Final Inspection12/7/200112/7/200112/7/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/7/2001 10:38:41 AM Fire life/safety finaled. Fire sprinkler finaled. Fire alarm given temp.
FIR01-00592 INSP-Final Inspection12/7/200112/7/200112/7/2001 12:00:00 AMAPART
Added by Inspector: 430 On 12/7/2001 10:40:58 AM SIgned temp per Sam Rogers. Sprinkler monitoring and duct shutdown on three units operating correctly. Inspection to be scheduled to test all other devices when operational.
FIR01-00401 INSP-Final Inspection12/7/200112/7/200112/7/2001 12:00:00 AMPFAIL
Added by Inspector: 430 On 12/7/2001 3:35:45 PM Provide tamper switches on control valves in riser room, provide tamper switch on dry pipe alarm trim, provide "Fire Sprinkler Room" sign on riser room, hard wire the air compressor, provide lock on fire alarm panel circuit, provide "knox box", provide map in knox box and at facp, provide low air pressure switch, verify single pressure switch is ok for two dry pipe risers, test exterior bell and sign
FIR01-00317 INSP-Sprinkler Rough-in12/7/200112/7/200112/7/2001 12:00:00 AMPPART
Holding cells and restrooms ok to cover 12/7/2001 4:00:27 PM
FIR01-00589 INSP-Final Inspection12/6/200112/7/200112/7/2001 12:00:00 AMPPASS
Fire alarm system finaled 12/7/2001 10:36:47 AM