Inspections for the day of: Tuesday, December 7, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02796 Electrical Rough-In12/6/200412/7/200412/7/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 12/6/2004 at 4:57:29 PM. Contact: ###-####. rest rms mech rm and outside walls 12/7/2004 8:03:38 AM
ELE04-03825 Temporary Service12/6/200412/7/200412/7/2004 12:00:00 AMAFAIL
###-#### - MIKE cor. met contractor, 110.3(B) needs neutral bus kit, shall not ID 6or smaller neutral, ID neutrals for 480 one way and 120 another 12/7/2004 9:15:25 AM
ELE04-03817 Permanent Service12/6/200412/7/200412/7/2004 12:00:00 AMANH
Scheduled by a contractor via Hello! on 12/6/2004 at 4:46:54 PM. Contact: ###-####. called notice posted 12/7/2004 8:44:35 AM
ELE04-03155 Electrical Rough-In12/6/200412/7/200412/7/2004 12:00:00 AMPNH
Jeff; Phone #: ###-#### Internet Inspection Request from: Jan Rice notice posted called left message 12/7/2004 2:55:10 PM
ELE04-03105 Final12/7/200412/7/200412/7/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 12/7/2004 at 7:54:28 AM. Contact: ###-####.
ELE04-03105 Final12/7/200412/7/200412/7/2004 12:00:00 AMPFAIL
please call for access information///brandon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore this is the 3rd correction posted pior violations not made, more created,300.15 needs box for splices cannot splice in the wall, 300.14 needs 6" of free conductor where wiremold extnsion box is used double fee due also posted called 12/7/2004 2:41:59 PM
ELE04-03317 Rough-In Permanent Service12/7/200412/7/200412/7/2004 12:00:00 AMPFAIL
Re-inspection. Please inspect asap. Thank you.; Phone #: ###-#### Internet Inspection Request from: Ken Litzinger cor. and reinspection fee posted all violation not corrected, outlet spacing, staple within 8"or 12" of boxes 334.30, 110.14 shall not mix copper and alum under same lug at p/s, 210.70(A)(3) LIGHT FOR FURNACE called u/g ok for cover only 12/7/2004 1:06:18 PM