Inspections for the day of: Wednesday, December 7, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04308 Electrical Rough-In12/7/200512/7/200512/7/2005 4:29:46 PMPCANC
jeff Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles did in morning
ELE05-04386 Electrical Rough-In12/7/200512/7/200512/7/2005 4:29:10 PMPPASS
Scheduled by a contractor via Hello! on 12/7/2005 at 9:46:38 AM. Contact: ###-####. walls only ok to cover
ELE05-03338 Final12/7/200512/7/200512/7/2005 4:06:19 PMPPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
ELE05-04236 Final12/7/200512/7/200512/7/2005 3:11:13 PMPFAIL
ceiling/final////stu; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 300.11(A) ceiling wires shall be identified, 800.154(A) abandoned comm wires shall be removed, 210.62 show room recpts shall be installed, 314.25 boxes shall have covers installed, 404.9(A) sws shall have covers installed,406.5 recpts shall shall have faceplates installed,408.4 circuit directory shall be complete and detailed, 800.24 communications cable shall be supported, BCC no violations shall be retained
ELE05-03956 Final12/7/200512/7/200512/7/2005 2:03:44 PMPCANC
Scheduled by a contractor via Hello! on 12/7/2005 at 7:52:02 AM. Contact: ###-####. see ri
ELE05-03344 Final12/7/200512/7/200512/7/2005 1:45:13 PMPPASS
spencer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corr made, ok to final
ELE05-04319 Final12/6/200512/7/200512/7/2005 1:10:01 PMPNH
DAN ; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, nh, not done
ELE05-04290 Electrical Rough-In12/7/200512/7/200512/7/2005 12:18:59 PMPPASS
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, ric walls only ok
ELE05-04131 Electrical Rough-In12/6/200512/7/200512/7/2005 11:44:26 AMAPASS
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford u/g ok to cover to light pole, and under slab
ELE05-04266 Final12/6/200512/7/200512/7/2005 10:07:00 AMACANC
NEED FINAL INSPECTION. ADDED CAN LIGHT AND OUTLETS TO SECOND FLOOR. STEVE WITH STERLING CONSTRUCTION WILL BE ON SITE. THANK YOU. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see ri
ELE05-04308 Electrical Rough-In12/7/200512/7/200512/7/2005 10:05:55 AMAPASS
inspection for underground conduit. located in the Nazareth Retreat Center parking area. Jeff on site ###-####; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to cover u/g
ELE05-04061 Conference12/6/200512/7/200512/7/2005 9:10:18 AMADONE
gary; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa reviewed wall spacing, 1 1/4", circuits etc
ELE05-04269 Electrical Rough-In12/6/200512/7/200512/7/2005 9:09:03 AMAPASS
mitch; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, talked to contr to change 1 box and a couple 1 1/4"
ELE05-04269 Permanent Service12/6/200512/7/200512/7/2005 8:33:50 AMAPASS
mitch; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h n ok
ELE05-04232 Rough-In Permanent Service12/6/200512/7/200512/7/2005 8:33:05 AMACANC
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, no access, he said bkr for power not identified yet either
ELE05-04266 Electrical Rough-In12/7/200512/7/200512/7/2005 12:00:00 AMAPASS
NEED FINAL INSPECTION. ADDED CAN LIGHT AND OUTLETS TO SECOND FLOOR. STEVE WITH STERLING CONSTRUCTION WILL BE ON SITE. THANK YOU. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH met with builder, need to fix 1 1/4" 3 plcs, ric ok
ELE05-03956 Electrical Rough-In12/7/200512/7/200512/7/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/7/2005 at 7:52:02 AM. Contact: ###-####. clg cover upstairs ok