FIR06-00716
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 3:30:41 PM | P | PASS |
|
|
Fire alarm test is acceptable, inspection passed, permit finaled.
|
FIR06-00568
| INSP-Final Inspection | 11/28/2006 | 12/7/2006 | 12/7/2006 3:27:34 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR06-00568
| INSP-Alarm Testing | 11/28/2006 | 12/7/2006 | 12/7/2006 3:27:06 PM | A | PASS |
|
|
Alarm testing passed.
|
FIR06-00519
| INSP-Final Inspection | 11/28/2006 | 12/7/2006 | 12/7/2006 3:26:34 PM | A | PASS |
|
|
Fire alarm work passed final inspection.
|
FIR06-00728
| INSP-Sprinkler Rough-in/Hydro | 12/6/2006 | 12/7/2006 | 12/7/2006 3:25:13 PM | A | PART |
|
|
UG hydrostatic test for the fire supply line completed satisfactory.
|
FIR06-00863
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 3:24:08 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
BLD06-02819
| FIRE-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 3:23:44 PM | A | PASS |
|
|
Life safety inspection passed, noted missing max. occupant load sign per review notes to be verified for compliance prior to structural final.
|
BLD06-01855
| FIRE-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 3:21:54 PM | A | PASS |
|
|
Fire life safety passed final inspection.
|
FIR05-00695
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 11:52:44 AM | A | FAIL |
|
|
Inspection conducted was for the 7th floor not including the sprinkler monitoring, FJ, and elevator recall. Noted three strobes in the main corridor with incorrect cd, SD in two rooms 728 and 730 are blocked by beams, the HC accessible room strobe notification device must function on general alarm, the "doorbell strobe" device violates IFC 2003 901.4.4.
|