Inspections for the day of: Thursday, December 7, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00836 INSP-Final Inspection12/7/200612/7/200612/7/2006 10:10:00 PMPFAIL
Finished testing the fire alarm connections for this permit which included jockey pump tamper, tank supply tamper, tank fill tamper and the first floor tamper and flow switch. Inspection was stopped when the first duct smoke detector inspected had the sample tube pointing the wrong way.
FIR06-00239 INSP-Final Inspection12/7/200612/7/200612/7/2006 10:08:16 PMPCANC
wrong inspection called in
BLD05-01989 FIRE-Final Inspection12/7/200612/7/200612/7/2006 10:07:28 PMPPASS
life safety finaled
BLD05-01990 FIRE-Final Inspection12/7/200612/7/200612/7/2006 10:07:11 PMPPASS
Life safety finaled
BLD05-01991 FIRE-Final Inspection12/7/200612/7/200612/7/2006 10:06:54 PMPPASS
Life safety finaled.
BLD06-01376 FIRE-Final Inspection12/7/200612/7/200612/7/2006 2:19:56 PMPFAIL
Provide correct suite number, lower fire extinguisher and provide with annual inspection tag, provide door hardware that unlocks in a single motion, hi-light sticker as discussed and provide the missing fire dept. review comments.
FIR06-00839 INSP-Final Inspection12/6/200612/7/200612/7/2006 2:16:55 PMPFAIL
See previous entry made for today.
FIR06-00839 INSP-Sprinkler Rough-in/Hydro12/6/200612/7/200612/7/2006 2:16:25 PMPFAIL
Hydro test is being cancelled. Not all of the tenant improvement work has been completed. There are heads missing along the east/west demizing wall and heads needing changed due to heater locations. Also on the south side shell area two upright heads are being blocked by light fixtures.
FIR06-00664 INSP-Sprinkler Rough-in/Hydro12/7/200612/7/200612/7/2006 12:51:11 PMPFAIL
There is a hole in the ground but no piping installed. No workers around and the contact does not answer the phone
FIR06-00756 INSP-Final Inspection12/7/200612/7/200612/7/2006 11:54:32 AMPPASS
permit finaled
FIR06-00220 INSP-Final Inspection12/7/200612/7/200612/7/2006 11:54:18 AMPPASS
Permit finaled
FIR06-00623 INSP-Sprinkler Rough-in12/6/200612/7/200612/7/2006 11:44:30 AMAPART
Sprinkler piping is ok to cover in the permited tenant areas only. The areas that have no tenant build outs at this time still need rough-in inspections
BLD06-00104 FIRE-Sprinkler Rough-in12/6/200612/7/200612/7/2006 11:43:15 AMAPASS
Sprinkler piping is ok to cover
BLD06-02192 FIRE-Sprinkler Rough-in12/6/200612/7/200612/7/2006 11:42:47 AMAPASS
Sprinkler piping is ok to cover
FIR06-00517 INSP-Final Inspection12/7/200612/7/200612/7/2006 11:02:34 AMPFAIL
Need to do forward flush and have the backflow certified.
FIR06-00832 INSP-Alarm Testing12/6/200612/7/200612/7/2006 11:01:46 AMAFAIL
Basically no test was performed. Phone line two would not go into trouble when disconnected, pull station was mounted too high and the outside bell does not work. When all of this is fixed a full test will need to be performed.
FIR05-00582 INSP-Final Inspection12/6/200612/7/200612/7/2006 11:00:10 AMAPASS
Permit finaled
FIR06-00909 INSP-Final Inspection12/6/200612/7/200612/7/2006 10:12:49 AMPCANC
LET ME KNOW WHEN YOU CAN BE THERE... Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
FIR05-00822 INSP-Sprinkler Rough-in12/6/200612/7/200612/7/2006 9:50:12 AMAPASS
The sprinkler piping under the balcony is ok to cover
FIR06-00872 INSP-Sprinkler Rough-in12/6/200612/7/200612/7/2006 9:20:26 AMAFAIL
No access
FIR06-00752 INSP-Sprinkler Rough-in/Hydro12/6/200612/7/200612/7/2006 9:06:00 AMAPART
Started 24 hr air test at 9:00am with 40 psi