FIR05-00836
| INSP-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 10:10:00 PM | P | FAIL |
|
|
Finished testing the fire alarm connections for this permit which included jockey pump tamper, tank supply tamper, tank fill tamper and the first floor tamper and flow switch. Inspection was stopped when the first duct smoke detector inspected had the sample tube pointing the wrong way.
|
FIR06-00239
| INSP-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 10:08:16 PM | P | CANC |
|
|
wrong inspection called in
|
BLD05-01989
| FIRE-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 10:07:28 PM | P | PASS |
|
|
life safety finaled
|
BLD05-01990
| FIRE-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 10:07:11 PM | P | PASS |
|
|
Life safety finaled
|
BLD05-01991
| FIRE-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 10:06:54 PM | P | PASS |
|
|
Life safety finaled.
|
BLD06-01376
| FIRE-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 2:19:56 PM | P | FAIL |
|
|
Provide correct suite number, lower fire extinguisher and provide with annual inspection tag, provide door hardware that unlocks in a single motion, hi-light sticker as discussed and provide the missing fire dept. review comments.
|
FIR06-00839
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 2:16:55 PM | P | FAIL |
|
|
See previous entry made for today.
|
FIR06-00839
| INSP-Sprinkler Rough-in/Hydro | 12/6/2006 | 12/7/2006 | 12/7/2006 2:16:25 PM | P | FAIL |
|
|
Hydro test is being cancelled. Not all of the tenant improvement work has been completed. There are heads missing along the east/west demizing wall and heads needing changed due to heater locations. Also on the south side shell area two upright heads are being blocked by light fixtures.
|
FIR06-00664
| INSP-Sprinkler Rough-in/Hydro | 12/7/2006 | 12/7/2006 | 12/7/2006 12:51:11 PM | P | FAIL |
|
|
There is a hole in the ground but no piping installed. No workers around and the contact does not answer the phone
|
FIR06-00756
| INSP-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 11:54:32 AM | P | PASS |
|
|
permit finaled
|
FIR06-00220
| INSP-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 11:54:18 AM | P | PASS |
|
|
Permit finaled
|
FIR06-00623
| INSP-Sprinkler Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 11:44:30 AM | A | PART |
|
|
Sprinkler piping is ok to cover in the permited tenant areas only. The areas that have no tenant build outs at this time still need rough-in inspections
|
BLD06-00104
| FIRE-Sprinkler Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 11:43:15 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD06-02192
| FIRE-Sprinkler Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 11:42:47 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
FIR06-00517
| INSP-Final Inspection | 12/7/2006 | 12/7/2006 | 12/7/2006 11:02:34 AM | P | FAIL |
|
|
Need to do forward flush and have the backflow certified.
|
FIR06-00832
| INSP-Alarm Testing | 12/6/2006 | 12/7/2006 | 12/7/2006 11:01:46 AM | A | FAIL |
|
|
Basically no test was performed. Phone line two would not go into trouble when disconnected, pull station was mounted too high and the outside bell does not work. When all of this is fixed a full test will need to be performed.
|
FIR05-00582
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 11:00:10 AM | A | PASS |
|
|
Permit finaled
|
FIR06-00909
| INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 10:12:49 AM | P | CANC |
|
|
LET ME KNOW WHEN YOU CAN BE THERE... Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|
FIR05-00822
| INSP-Sprinkler Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 9:50:12 AM | A | PASS |
|
|
The sprinkler piping under the balcony is ok to cover
|
FIR06-00872
| INSP-Sprinkler Rough-in | 12/6/2006 | 12/7/2006 | 12/7/2006 9:20:26 AM | A | FAIL |
|
|
No access
|
FIR06-00752
| INSP-Sprinkler Rough-in/Hydro | 12/6/2006 | 12/7/2006 | 12/7/2006 9:06:00 AM | A | PART |
|
|
Started 24 hr air test at 9:00am with 40 psi
|