Inspections for the day of: Friday, December 7, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03553 Final12/7/200712/7/200712/7/2007 4:16:17 PMPPASS
fianl on remodel. any questions call Jimmy @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose called contractor, somebody added floor heat, not inspected, ok to final what could see
ELE07-04034 Electrical Rough-In12/6/200712/7/200712/7/2007 3:26:18 PMPPASS
Rough inspection and ufer inspection Phone #: ###-#### Internet Inspection Request from: Monty Adkinson correction for ri only made, concrete encased electrode shall have clean-up for stem wall to remove mud and black substance removed from concrete. They will re-call for electrode.
ELE07-03463 Final12/7/200712/7/200712/7/2007 2:27:50 PMPPASS
jean - please call 1/2 hr prior to inspection Phone #: ###-#### call contractor, ok to final
ELE06-03143 Electrical Rough-In12/7/200712/7/200712/7/2007 1:38:21 PMPPASS
ed Phone #: ###-#### ok to temporary cover ceiling sw office, 3rd floor about 3 rows tile until new nw part starts
ELE07-04046 Rough-In Permanent Service12/6/200712/7/200712/7/2007 12:53:42 PMPPASS
kevin Phone #: ###-#### ric ok for service, p/s u/g rec ok (new u/g) was o/h
ELE07-03445 Permanent Service12/6/200712/7/200712/7/2007 10:45:17 AMACANC
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contractor, told passed yesterday, talked about grounding at service
ELE06-00320 Final12/6/200712/7/200712/7/2007 10:32:40 AMAFAIL
robert Note: please call 1/2 hr prior to be open Phone #: ###-#### met owner, left correction notice, nec 406.8(B) outdoor receptacles shall have weatherproof covers installed whether or not cord is in use, 210.12(B) dwelling unit bedrooms shall be protected by arc fault circuit interrupters, 410.8(B) closet fixtures shall have completely enclosed lamp, 410.8(D) closet fixtures shall be 12" from edge of shelves for incandescent and 6" for fluorescent
ELE07-04045 Electrical Rough-In12/6/200712/7/200712/7/2007 9:41:23 AMAPASS
jessie Phone #: ###-#### ric ok
ELE07-04045 Final12/7/200712/7/200712/7/2007 9:33:00 AMAPASS
jessie Phone #: ###-#### ok to final
ELE07-03493 Final12/6/200712/7/200712/7/2007 9:05:44 AMAPASS
Access code is 1290. Any Questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan called contractor, ok to final
ELE07-03970 Electrical Rough-In12/6/200712/7/200712/7/2007 8:15:32 AMAPASS
Scheduled by a contractor via Hello! on 12/6/2007 at 1:34:15 PM. Contact: ###-####. called contr, they are changing address again, u/g ok to cover in slab, told contractor to put cover on meter pak and provide clearance at service- remove tree and shrubs
ELE07-03493 Permanent Service12/6/200712/7/200712/6/2007 8:17:39 PMACANC
Any questions or concerns please call Clay at ###-####. Access code is 1290. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan Inspection cancelled from web by: Clay Morgan