Inspections for the day of: Friday, December 7, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01160 Final12/7/200712/7/200712/7/2007 5:36:00 PMPNR
Scheduled by a contractor via Hello! on 12/7/2007 at 7:30:07 AM. Contact: ###-####.
. 1. site is not ready at this time. .
. 2. still under construction. .
ELE07-01158 Final12/7/200712/7/200712/7/2007 5:34:59 PMPPASS
Scheduled by a contractor via Hello! on 12/7/2007 at 7:28:42 AM. Contact: ###-####.
. 1. final ok, see the survey note. .
. 2. survey note --- recep spacing in one room, 6' -- 12' rule, 210.52. .
ELE07-01174 Final12/7/200712/7/200712/7/2007 4:38:03 PMPPASS
Scheduled by a contractor via Hello! on 12/7/2007 at 7:27:02 AM. Contact: ###-####.
. 1. final ok. .
. 2. survey note -- recep spacing in one room, 6' -- 12' rule, 210.52. .
ELE07-01154 Final12/7/200712/7/200712/7/2007 3:36:12 PMPFAIL
Scheduled by a contractor via Hello! on 12/7/2007 at 7:25:27 AM. Contact: ###-####.
. 1. 110.26.A. Working clearance of the panel ---- remove the shelf and closet rod that are above the panel in the laundry room. .
ELE07-02246 Final12/7/200712/7/200712/7/2007 3:04:31 PMPFAIL
Scheduled by a contractor via Hello! on 12/7/2007 at 7:23:53 AM. Contact: ###-####.
. 1. panel in closet mstr bdrm, general contractor stated that they would build a wall to seperate the panel from the closet. .
ELE07-02246 Final12/7/200712/7/200712/7/2007 3:02:43 PMPFAIL
Scheduled by a contractor via Hello! on 12/7/2007 at 7:23:53 AM. Contact: ###-####.
. 1. 240.24.D. Overcurrent devices shall not be located in clothes closet (mstrbdrm). .
. 2. The rest of the inspection was ok, with the exception of the survey note. .
. 3. survey note --- recep spacing in mstr bdrm. .
ELE07-01146 Electrical Rough-In12/7/200712/7/200712/7/2007 2:57:10 PMPPASS
Scheduled by a contractor via Hello! on 12/7/2007 at 7:22:00 AM. Contact: ###-####.
. 1. ri ok. .
ELE07-04015 Final12/6/200712/7/200712/7/2007 1:05:44 PMPNH
TOBY SERVICE CHANGE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
. 1. no access, spoke with contractor and let him know how to make an appointment for the first slot in the am or pm. .
. 2. they will reschedule for monday or tuesday. .
ELE07-03742 Final12/7/200712/7/200712/7/2007 12:54:29 PMPPASS
final on new service, new shop and service on house. Phone #: ###-#### Internet Inspection Request from: Andy Rose
. 1. final ok. .
ELE07-03188 Final12/6/200712/7/200712/7/2007 11:55:41 AMAPASS
Ed Phone #: ###-####
. 1. final ok. .
ELE07-04041 Rough-In Permanent Service12/6/200712/7/200712/7/2007 10:13:08 AMACANC
tom Phone #: ###-####
. 1. no permanent service at this time, see rough-in for this date. .
ELE07-04041 Electrical Rough-In12/7/200712/7/200712/7/2007 10:11:59 AMPPASS
tom Phone #: ###-####
. 1. underground from the house to the garage ok. .
ELE07-04001 Rough-In Permanent Service12/6/200712/7/200712/7/2007 10:01:21 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk
. 1. ri ok. .
. 2. p/s u/g n ok. .
ELE07-04042 Rough-In Permanent Service12/6/200712/7/200712/7/2007 9:32:16 AMACANC
tom Phone #: ###-####
. 1. there is no permanent service at this time, see the rough-in for this date. .
ELE07-04042 Electrical Rough-In12/7/200712/7/200712/7/2007 9:30:17 AMPPASS
tom Phone #: ###-####
. 1. underground from house to garage is ok. .
ELE07-03868 Electrical Rough-In12/6/200712/7/200712/7/2007 8:35:18 AMAFAIL
U-Fer Ground Inspection only. Concrete guys want to pour after 1pm Friday, December 07,2007. Thank you. Phone #: ###-#### Internet Inspection Request from: Paula Gietzen
. 1. Electrode not in proper position, needs to be on the bottom of the footing. .