Inspections for the day of: Wednesday, December 7, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02696 FIRE-Final Inspection12/7/201112/7/201112/8/2011 10:50:40 AMPPART
Reviewed permit documents on site, noted missing max. occupant load signs, need approved hardware at the second exit east side, post "door to remain..."signage. PFE's provided.
FIR11-00639 INSP-Sprinkler Rough-in12/7/201112/7/201112/7/2011 2:55:05 PMPPART
Overhead work at suite 330 approved for ceiling cover.
FIR08-00604 INSP-Alarm Testing12/7/201112/7/201112/7/2011 2:16:04 PMPNR
Low air pressure switches at dry systems not set, DH did not release, noted 4th floor dry system LAPS activated a general alarm condition.
FIR11-00534 INSP-Sprinkler Rough-in/Hydro12/7/201112/7/201112/7/2011 2:12:31 PMPFAIL
Antifreeze system hydrostatic test failed due to visible leakage and a pressure drop at the guage.
FIR11-00618 INSP-Sprinkler Rough-in/Hydro12/7/201112/7/201112/7/2011 2:11:05 PMPPART
Rough-in passed with the exception of two missing hangers and sprinklers at two locations to be changed to the correct temp. rating. Corrections can be verified at final inspection prior to occupancy.
BLD11-02696 FIRE-Final Inspection12/7/201112/7/201112/7/2011 12:25:20 PMANR
C/N incomplete
FIR11-00534 INSP-Sprinkler Rough-in/Hydro12/7/201112/7/201112/7/2011 12:19:34 PMAPART
Overhead hydrostatic testing for the basement and 1st floor levels passed.
FIR11-00534 INSP-Sprinkler Rough-in12/6/201112/7/201112/7/2011 12:17:31 PMAPART
Completed overhead inspection for the 1st floor. Correction items include; 3 upright heads at the antifreeze system elevated entryway west side, provide revised plans including changes for sprinkler protection at the test chamber 138 within the calc area and added sw heads for garage doors, add missing seismic bracing at the 3" main, verify correct size hangers for 4" main. Drop ceiling areas okayed for cover.