Inspections for the day of: Friday, December 7, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00394 FIR-Aging Inspection12/7/201212/7/201212/7/2012 4:31:50 PM PEND
FIR12-00478 FIR-Aging Inspection12/7/201212/7/201212/7/2012 4:30:18 PM PEND
Need site inspection request when work is complete.
FIR12-00246 INSP-Sprinkler Rough-in/Hydro12/7/201212/7/201212/7/2012 4:27:00 PMPPART
Concluded satisfactory air test of the new dry system with no pressure loss at the guage. Also finished hydrostatic testing of the wet system.
FIR12-00604 INSP-Sprinkler Rough-in/Hydro12/7/201212/7/201212/7/2012 4:22:23 PMPPART
Overhead hydrostatic re-test passed for both the first and second floors.
BLD12-03071 FIRE-Final Inspection12/6/201212/7/201212/7/2012 4:21:26 PMANR
Need to provide access for inspection as discussed. On site review of permit documents and initial walkthrough completed.
BLD12-03072 FIRE-Final Inspection12/6/201212/7/201212/7/2012 4:20:38 PMANR
Need to provide access for inspection as discussed. On site review of permit documents and initial walkthrough completed.
FIR12-00570 INSP-Final Inspection12/6/201212/7/201212/7/2012 4:18:30 PMAPART
Overhead fire sprinkler system modifications okayed for cover at the remodeled areas. As-builts accepted.