ELE15-03396
| Electrical Rough-In | 12/7/2015 | 12/7/2015 | 12/7/2015 3:07:18 PM | P | PASS |
|
|
underground Phone #: ###-#### East electrical room rough in ok cover
|
ELE15-03913
| Final | 12/7/2015 | 12/7/2015 | 12/7/2015 2:30:38 PM | P | PASS |
|
|
Mike Phone #: ###-#### Corrections made. Final ok
|
ELE15-03913
| Electrical Rough-In | 12/7/2015 | 12/7/2015 | 12/7/2015 2:23:59 PM | P | PASS |
|
|
Mike Phone #: ###-#### Garage and underground rough in ok cover
|
GCE15-00168
| GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 2:09:13 PM | P | FAIL |
|
|
Brandon ###-#### 110.12(B)- Wiring shall not be damaged. Range wire split above box. repair or replace. 310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used. Either change to #1 SER or fuse down to 80 amp max. 334.30- Max span for support of NM cable shall not exceed 4 1/2'. 10-3 on 2nd floor.
|
GCE15-00167
| GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 2:08:51 PM | P | FAIL |
|
|
Brandon ###-#### 310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used either change to #1 SER or fuse down to 80 amp max. 314.25- All boxes shall have covers. Can on front of garage cover not installed properly.
|
ELE11-02817
| ELE-Aging Inspection | 12/7/2015 | 12/7/2015 | 12/7/2015 10:02:09 AM | | DONE |
|
|
Waiting on contractor
|
ELE15-03840
| Final | 12/4/2015 | 12/7/2015 | 12/7/2015 9:32:44 AM | A | FAIL |
|
|
Scott. Correction made. Phone #: ###-#### Inspection requested via web by Sean DeLacy Correction not complete. 300.15- All cables and conduits shall terminate in a box.
|