Inspections for the day of: Monday, December 7, 2015.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03396 Electrical Rough-In12/7/201512/7/201512/7/2015 3:07:18 PMPPASS
underground Phone #: ###-#### East electrical room rough in ok cover
ELE15-03913 Final12/7/201512/7/201512/7/2015 2:30:38 PMPPASS
Mike Phone #: ###-#### Corrections made. Final ok
ELE15-03913 Electrical Rough-In12/7/201512/7/201512/7/2015 2:23:59 PMPPASS
Mike Phone #: ###-#### Garage and underground rough in ok cover
GCE15-00168 GCE-Rough-In Permanent Service12/4/201512/7/201512/7/2015 2:09:13 PMPFAIL
Brandon ###-####
110.12(B)- Wiring shall not be damaged. Range wire split above box. repair or replace.
310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used. Either change to #1 SER or fuse down to 80 amp max.
334.30- Max span for support of NM cable shall not exceed 4 1/2'. 10-3 on 2nd floor.
GCE15-00167 GCE-Rough-In Permanent Service12/4/201512/7/201512/7/2015 2:08:51 PMPFAIL
Brandon ###-####
310.15(B)(7)- #2 SER will be surrounded by thermal insulation, 60 degree column shall be used either change to #1 SER or fuse down to 80 amp max.
314.25- All boxes shall have covers. Can on front of garage cover not installed properly.
ELE11-02817 ELE-Aging Inspection12/7/201512/7/201512/7/2015 10:02:09 AM DONE
Waiting on contractor
ELE15-03840 Final12/4/201512/7/201512/7/2015 9:32:44 AMAFAIL
Scott. Correction made. Phone #: ###-#### Inspection requested via web by Sean DeLacy Correction not complete. 300.15- All cables and conduits shall terminate in a box.