ELE11-02621
| ELE-Aging Inspection | 12/7/2015 | 12/7/2015 | 12/8/2015 8:00:00 AM | | DONE |
|
|
too busy
|
ELE12-01307
| ELE-Aging Inspection | 12/7/2015 | 12/7/2015 | 12/8/2015 7:59:27 AM | | DONE |
|
|
too busy
|
ELE15-03915
| Rough-In Permanent Service | 12/7/2015 | 12/7/2015 | 12/7/2015 4:17:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder r/i ok p/s u/g n ok
|
ELE15-03855
| Electrical Rough-In | 12/4/2015 | 12/7/2015 | 12/7/2015 3:38:43 PM | P | PASS |
|
|
If you have any questions, please call Clay. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan r/i walls ok
|
ELE15-02960
| Electrical Rough-In | 12/7/2015 | 12/7/2015 | 12/7/2015 3:14:58 PM | P | PASS |
|
|
One Capital Center, Level 11 ceiling inspection. Contact Jon Novak. Phone #: ###-#### Inspection requested via web by Cathy Duchek r/i northeast ceilings ok
|
GCE15-00169
| GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 2:14:02 PM | P | FAIL |
|
|
Brandon ###-#### 310.15(B)(7)- #2 alum only good for 75amps. OK to install 80 amp breaker as per 240.4(B) 300.4(A)(1)- nailplates need upst. bdrms, kitchen, upst. bath. 334.30-support and secure ser at sub panel and main service. load calcs recommended for sub panel
|
GCE15-00166
| GCE-Rough-In Permanent Service | 12/4/2015 | 12/7/2015 | 12/7/2015 2:13:03 PM | P | FAIL |
|
|
Brandon ###-#### 310.15(B)(7)- #2 alum ser only rated for 75 amps.80 amp breaker ok as per 240.4(B) 300.4(A)(1)- nailplates needed above sub panel. Load calcs recommended for sub panel
|
ELE12-00137
| ELE-Aging Inspection | 12/7/2015 | 12/7/2015 | 12/7/2015 9:40:06 AM | | DONE |
|
|
left message to call in for final
|
ELE15-03770
| Final | 12/4/2015 | 12/7/2015 | 12/7/2015 9:34:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Sellman final ok
|
ELE15-03907
| Final | 12/6/2015 | 12/7/2015 | 12/7/2015 8:44:32 AM | A | NH |
|
|
Equipment bonding Phone #: ###-#### Inspection requested via web by michael hunt no access
|