Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03892 Electrical Rough-In12/7/201512/7/201512/7/2015 2:45:46 PMPFAIL
Rod Phone #: ###-#### NEC 300.4 Nail Plates needed NEC 300.4 Cables and raceways paralled to framing member shall not be less than 1 1/4 from the nearest edge. NEC 362.12(9) ENT shall not be installed where subject to phyical damage. NEC 362.30 Securing and supporting with-in 3ft of an outlet box and at intervals exceeding 3ft.