ELE16-03822
| Electrical Rough-In | 12/7/2016 | 12/7/2016 | 12/7/2016 3:08:49 PM | P | PASS |
|
|
Inspection of hard lid areas prior to cover. Phone #: ###-#### Inspection requested via web by Steve Craig Hard lids only. Contractor to do fire alarm wiring when approved. Area noted rough in ok cover
|
ELE16-03135
| Final | 12/6/2016 | 12/7/2016 | 12/7/2016 3:07:15 PM | P | PART |
|
|
Please call Kyle for any questions or concerns. Phone #: ###-#### Inspection requested via web by Kyle Lott 210.8- Receptacle near furnace to left of stair with in 6' of sink shall have GFCI protection. 314.23- Boxes shall be securely mounted. ceiling in front of stair and niche by ramp. 358.30- EMT shall be secured with in 3' of a box. room in front of stair. 406.6- Receptacles mounted to face plate shall cover box completely. Cover not secured to box in room to far right of stair. Contractor to repair today. TCO ok
|
ELE15-02960
| Final | 12/5/2016 | 12/7/2016 | 12/7/2016 1:58:30 PM | P | PASS |
|
|
Final Inspection Contact Jon Novak Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek All work noted by Rex Boyles is all work done just need to final. Final ok
|
ELE16-03517
| Temporary Service | 12/7/2016 | 12/7/2016 | 12/7/2016 1:54:59 PM | P | PASS |
|
|
###-#### Moved temp pole reinspect for grounding electode system. Connection to ground rod loose contractor to re-tighten connection. t/s o/h rec ok
|
ELE16-02068
| Final | 12/6/2016 | 12/7/2016 | 12/7/2016 10:51:50 AM | A | FAIL |
|
|
Garage code is JAYO enter.. This house has an AC prewired they are not going to install it at this time. Phone #: ###-#### Inspection requested via web by Zane Robertson 210.8- All 120 volt 15 and 20 amp receptacles located within 6' of a sink shall have GFCI protection. Washer 210.52(B)- No point measured on kitchen counter top shall be more than 24" from a receptacle outlet. Area under micro 40"
|
ELE16-03956
| Temporary Service | 12/6/2016 | 12/7/2016 | 12/7/2016 9:42:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Work space may not be present depending on where set near transformer. t/s u/g n ok
|
ELE16-03959
| Temporary Service | 12/7/2016 | 12/7/2016 | 12/7/2016 9:17:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE16-03960
| Temporary Service | 12/7/2016 | 12/7/2016 | 12/7/2016 9:12:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|