Inspections for the day of: Wednesday, December 7, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03822 Electrical Rough-In12/7/201612/7/201612/7/2016 3:08:49 PMPPASS
Inspection of hard lid areas prior to cover. Phone #: ###-#### Inspection requested via web by Steve Craig
Hard lids only. Contractor to do fire alarm wiring when approved. Area noted rough in ok cover
ELE16-03135 Final12/6/201612/7/201612/7/2016 3:07:15 PMPPART
Please call Kyle for any questions or concerns. Phone #: ###-#### Inspection requested via web by Kyle Lott
210.8- Receptacle near furnace to left of stair with in 6' of sink shall have GFCI protection.
314.23- Boxes shall be securely mounted. ceiling in front of stair and niche by ramp.
358.30- EMT shall be secured with in 3' of a box. room in front of stair.
406.6- Receptacles mounted to face plate shall cover box completely. Cover not secured to box in room to far right of stair.
Contractor to repair today. TCO ok
ELE15-02960 Final12/5/201612/7/201612/7/2016 1:58:30 PMPPASS
Final Inspection
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
All work noted by Rex Boyles is all work done just need to final. Final ok
ELE16-03517 Temporary Service12/7/201612/7/201612/7/2016 1:54:59 PMPPASS
###-#### Moved temp pole reinspect for grounding electode system.
Connection to ground rod loose contractor to re-tighten connection. t/s o/h rec ok
ELE16-02068 Final12/6/201612/7/201612/7/2016 10:51:50 AMAFAIL
Garage code is JAYO enter.. This house has an AC prewired they are not going to install it at this time. Phone #: ###-#### Inspection requested via web by Zane Robertson
210.8- All 120 volt 15 and 20 amp receptacles located within 6' of a sink shall have GFCI protection. Washer
210.52(B)- No point measured on kitchen counter top shall be more than 24" from a receptacle outlet. Area under micro 40"
ELE16-03956 Temporary Service12/6/201612/7/201612/7/2016 9:42:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey
Work space may not be present depending on where set near transformer. t/s u/g n ok
ELE16-03959 Temporary Service12/7/201612/7/201612/7/2016 9:17:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE16-03960 Temporary Service12/7/201612/7/201612/7/2016 9:12:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok