ELE16-01473
| Electrical Rough-In | 12/7/2016 | 12/7/2016 | 12/7/2016 2:57:21 PM | P | PASS |
|
|
ceiling only ok to cover
|
ELE16-03578
| Temporary Service | 12/7/2016 | 12/7/2016 | 12/7/2016 2:55:48 PM | P | PASS |
|
|
Contact is Rene Ramakers at ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell t/s o/h n ok
|
ELE16-00768
| Electrical Rough-In | 12/7/2016 | 12/7/2016 | 12/7/2016 2:34:58 PM | P | PASS |
|
|
Underground inspection for pool area Phone #: ###-#### Inspection requested via web by Tracy Robertson Underground back side of pool ok to cover
|
ELE16-03116
| Permanent Service | 12/7/2016 | 12/7/2016 | 12/7/2016 1:37:23 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Need to pull sub panel feeders and land conductors before Perm Serve can be passed
|
ELE16-03955
| Temporary Service | 12/6/2016 | 12/7/2016 | 12/7/2016 1:08:26 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE16-03915
| Electrical Rough-In | 12/7/2016 | 12/7/2016 | 12/7/2016 12:34:11 PM | P | PASS |
|
|
we will get there at noon. Phone #: ###-#### Inspection requested via web by Tim Dunlop Walked project, checked UL listing of parts. Rough in ok
|
ELE16-01866
| Final | 12/6/2016 | 12/7/2016 | 12/7/2016 9:27:02 AM | A | FAIL |
|
|
Phone #: ###-#### 680.51(A) Submersible pumps Shall have GFCI protection. (Back Fountain) 406.12 A Tamper reasistant Receps shall be installed in dwelling units ( Kitchen Receps) 314.20 Boxes set back 1/4in shall have spark rings. ( KItchen back splash)
|
ELE16-03847
| Conference | 12/2/2016 | 12/7/2016 | 12/7/2016 8:29:55 AM | A | DONE |
|
|
Fred// please call ahead Phone #: ###-#### Spoke about Code Ref. 240.21(1) (1). Tap rule for adding 50A sub panel next to 200A main disc on house. Informed to make sure all luggs and equipment are rated for use.
|