Inspections for the day of: Wednesday, December 7, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01473 Electrical Rough-In12/7/201612/7/201612/7/2016 2:57:21 PMPPASS
ceiling only ok to cover
ELE16-03578 Temporary Service12/7/201612/7/201612/7/2016 2:55:48 PMPPASS
Contact is Rene Ramakers at ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell t/s o/h n ok
ELE16-00768 Electrical Rough-In12/7/201612/7/201612/7/2016 2:34:58 PMPPASS
Underground inspection for pool area Phone #: ###-#### Inspection requested via web by Tracy Robertson Underground back side of pool ok to cover
ELE16-03116 Permanent Service12/7/201612/7/201612/7/2016 1:37:23 PMPNR
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Need to pull sub panel feeders and land conductors before Perm Serve can be passed
ELE16-03955 Temporary Service12/6/201612/7/201612/7/2016 1:08:26 PMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-03915 Electrical Rough-In12/7/201612/7/201612/7/2016 12:34:11 PMPPASS
we will get there at noon. Phone #: ###-#### Inspection requested via web by Tim Dunlop Walked project, checked UL listing of parts. Rough in ok
ELE16-01866 Final12/6/201612/7/201612/7/2016 9:27:02 AMAFAIL
Phone #: ###-#### 680.51(A) Submersible pumps Shall have GFCI protection. (Back Fountain) 406.12 A Tamper reasistant Receps shall be installed in dwelling units ( Kitchen Receps) 314.20 Boxes set back 1/4in shall have spark rings. ( KItchen back splash)
ELE16-03847 Conference12/2/201612/7/201612/7/2016 8:29:55 AMADONE
Fred// please call ahead Phone #: ###-#### Spoke about Code Ref. 240.21(1) (1). Tap rule for adding 50A sub panel next to 200A main disc on house. Informed to make sure all luggs and equipment are rated for use.