Inspections for the day of: Thursday, December 7, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01337 Permanent Service12/6/201712/7/201712/7/2017 3:16:58 PMPFAIL
We are requesting a permanent service inspection for tomorrow afternoon. Also need a rough-in for 4th rm# 422 ; 438 and 2nd ; 3rd floor hallways. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
110.24- Available fault current shall be posted prior to permenant inspection.
65K rated main 6x600kcmil service entrance conductors 2520 amp rating.
ELE17-01337 Electrical Rough-In12/7/201712/7/201712/7/2017 3:04:31 PMPPART
We are requesting a permanent service inspection for tomorrow afternoon. Also need a rough-in for 4th rm# 422 ; 438 and 2nd ; 3rd floor hallways. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Level 3 ceiling insulated prior to inspection, shall be removed.
West stairway not ready,
level 1 work area walls,
level 2 hall fire lid,
level 4 rooms 422 and 438
Areas noted rough in ok cover
ELE17-02821 Final12/7/201712/7/201712/7/2017 2:09:13 PMPPASS
Ron Phone #: ###-####
Final ok
ELE17-04065 Conference12/7/201712/7/201712/7/2017 2:08:38 PMPDONE
As per head structural Bob Archibald. Due to plan review on building permit being completed prior to 7-1-17 the 2014 version of NEC will apply.
ELE17-02183 Electrical Rough-In12/7/201712/7/201712/7/2017 1:36:27 PMPPASS
Rock
I need to be there to meet you so i will work my lunch around you if need be.
I leave for day at 3:30 ish.
Mike Phone #: ###-#### Inspection requested via web by Mike Cole
North family rm ok, formal dining not walls open, Main family rm no open walls, piano rm ok, entry ok, guest bed and bath ok, master bed and bath ok, all upstairs ok. Some circuits ungrounded. Areas noted rough in ok cover
ELE17-03439 Final12/5/201712/7/201712/7/2017 11:12:19 AMAPASS
Phone #: ###-#### Inspection requested via web by sam petterson
Final ok
ELE17-01549 Electrical Rough-In12/6/201712/7/201712/7/2017 10:29:38 AMANR
Underground. Main Street. Shane is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Called contact and he stated conduit not installed yet will recall when ready.
ELE17-04117 Electrical Rough-In12/6/201712/7/201712/7/2017 10:16:13 AMAPASS
Please contact Matt Bruns with any questions

This is a wall rough-in inspection

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Called contact to discuss 210.71 he stated he was aware of requirements. Conf. rm 302 is 228 sq.ft., 6 receptacles, rm 304 is 303 sq.ft., 7 receptacles, rm 311 is 235 sq.ft. 6 receptacles, rm 316 part of phase 2. Rooms 301 thru 311 and 326 thru 328 wall rough in ok cover
ELE17-03869 Temporary Service12/6/201712/7/201712/7/2017 9:26:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok
ELE17-03872 Temporary Service12/6/201712/7/201712/7/2017 9:26:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
t/s u/g n ok