Inspections for the day of: Thursday, December 7, 2017.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02486 FIRE-Final Inspection12/6/201712/7/201712/7/2017 3:22:46 PMPFAIL
Provide correct hardware on all exit doors as discussed or provide plan review approval that they can be turned into windows by having hardware and exit signs removed. Exit discharge lights appear to be on a timer which is not allowed. provide missing exit sign at the north east exit door
BLD17-00763 FIRE-Final Inspection12/6/201712/7/201712/7/2017 3:20:38 PMPPASS
Bldg shell fire/life safety passed. Contractor is going to provide fire dept access signage tomorrow. WIll be verified with the T.I. final inspection
BLD17-00729 FIRE-Final Inspection12/6/201712/7/201712/7/2017 2:42:42 PMPFAIL
Life safety will be ok to sign off when the project fire alarm and fire sprinkler permits are finaled

MIke Phone #: ###-####
FIR17-00431 INSP-Final Inspection12/6/201712/7/201712/7/2017 2:40:27 PMPFAIL
All items tested ok except one of the three duct smoke detectors needs to be relocated to the narrow side of the rectangular duct and provided with the correct sample tube and re-tested.
FIR17-00433 INSP-Final Inspection12/7/201712/7/201712/7/2017 2:38:02 PMAFAIL
Need sticker for the bell and forward flow flush. Also will need test papers. Unit heaters have been installed in the wet system spaces in the attic above the main roof with temp. sensors.
BLD06-02324 FIRE-Final Inspection12/7/201712/7/201712/7/2017 1:06:22 PMAPART
Fire life safety passed in Suites, 101, 202, 207, 208, 301, 303, 304.
FIR17-00545 INSP-Sprinkler Rough-in/Hydro12/6/201712/7/201712/7/2017 12:57:55 PMPPASS
The overhead hydro for the MOB has passed and the corridor that connects the MOB to the existing hospital is ok for cover.
FIR17-00326 INSP-Supply line flush12/7/201712/7/201712/7/2017 10:42:49 AMPPASS
Underground flush passed
FIR17-00414 INSP-Supply line flush12/7/201712/7/201712/7/2017 10:42:20 AMPPASS
Underground flush passed
FIR17-00415 INSP-Supply line flush12/7/201712/7/201712/7/2017 10:41:50 AMPPASS
Underground flush passed
FIR17-00416 INSP-Supply line flush12/6/201712/7/201712/7/2017 10:40:15 AMAFAIL
Suez was unable to turn on valve so no flush was performed
FIR17-00667 INSP-Final Inspection12/6/201712/7/201712/7/2017 10:39:22 AMAPASS
Permit finaled
BLD17-03612 FIRE-Final Inspection12/6/201712/7/201712/7/2017 10:38:28 AMAFAIL
Provide emergency lighting through out all common spaces as discussed. All other items appear ok.
FIR16-00284 INSP-Final Inspection12/6/201712/7/201712/7/2017 9:15:23 AMAPASS
permit finaled
BLD06-02321 FIRE-Final Inspection12/6/201712/7/201712/7/2017 9:11:43 AMACANC
Come anytime. Call when you head our way Phone #: ###-#### >> Inspection requested via web by Bob Thornton Inspection cancelled from web by: Bob Thornton
FIR17-00679 INSP-Sprinkler Rough-in12/6/201712/7/201712/7/2017 7:24:02 AMAPASS
The remaining underground supply piping is ok for cover.

Jeremy-to cover Phone #: ###-####