BLD17-02486
| FIRE-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 3:22:46 PM | P | FAIL |
|
|
Provide correct hardware on all exit doors as discussed or provide plan review approval that they can be turned into windows by having hardware and exit signs removed. Exit discharge lights appear to be on a timer which is not allowed. provide missing exit sign at the north east exit door
|
BLD17-00763
| FIRE-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 3:20:38 PM | P | PASS |
|
|
Bldg shell fire/life safety passed. Contractor is going to provide fire dept access signage tomorrow. WIll be verified with the T.I. final inspection
|
BLD17-00729
| FIRE-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 2:42:42 PM | P | FAIL |
|
|
Life safety will be ok to sign off when the project fire alarm and fire sprinkler permits are finaled
MIke Phone #: ###-####
|
FIR17-00431
| INSP-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 2:40:27 PM | P | FAIL |
|
|
All items tested ok except one of the three duct smoke detectors needs to be relocated to the narrow side of the rectangular duct and provided with the correct sample tube and re-tested.
|
FIR17-00433
| INSP-Final Inspection | 12/7/2017 | 12/7/2017 | 12/7/2017 2:38:02 PM | A | FAIL |
|
|
Need sticker for the bell and forward flow flush. Also will need test papers. Unit heaters have been installed in the wet system spaces in the attic above the main roof with temp. sensors.
|
BLD06-02324
| FIRE-Final Inspection | 12/7/2017 | 12/7/2017 | 12/7/2017 1:06:22 PM | A | PART |
|
|
Fire life safety passed in Suites, 101, 202, 207, 208, 301, 303, 304.
|
FIR17-00545
| INSP-Sprinkler Rough-in/Hydro | 12/6/2017 | 12/7/2017 | 12/7/2017 12:57:55 PM | P | PASS |
|
|
The overhead hydro for the MOB has passed and the corridor that connects the MOB to the existing hospital is ok for cover.
|
FIR17-00326
| INSP-Supply line flush | 12/7/2017 | 12/7/2017 | 12/7/2017 10:42:49 AM | P | PASS |
|
|
Underground flush passed
|
FIR17-00414
| INSP-Supply line flush | 12/7/2017 | 12/7/2017 | 12/7/2017 10:42:20 AM | P | PASS |
|
|
Underground flush passed
|
FIR17-00415
| INSP-Supply line flush | 12/7/2017 | 12/7/2017 | 12/7/2017 10:41:50 AM | P | PASS |
|
|
Underground flush passed
|
FIR17-00416
| INSP-Supply line flush | 12/6/2017 | 12/7/2017 | 12/7/2017 10:40:15 AM | A | FAIL |
|
|
Suez was unable to turn on valve so no flush was performed
|
FIR17-00667
| INSP-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 10:39:22 AM | A | PASS |
|
|
Permit finaled
|
BLD17-03612
| FIRE-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 10:38:28 AM | A | FAIL |
|
|
Provide emergency lighting through out all common spaces as discussed. All other items appear ok.
|
FIR16-00284
| INSP-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 9:15:23 AM | A | PASS |
|
|
permit finaled
|
BLD06-02321
| FIRE-Final Inspection | 12/6/2017 | 12/7/2017 | 12/7/2017 9:11:43 AM | A | CANC |
|
|
Come anytime. Call when you head our way Phone #: ###-#### >> Inspection requested via web by Bob Thornton Inspection cancelled from web by: Bob Thornton
|
FIR17-00679
| INSP-Sprinkler Rough-in | 12/6/2017 | 12/7/2017 | 12/7/2017 7:24:02 AM | A | PASS |
|
|
The remaining underground supply piping is ok for cover.
Jeremy-to cover Phone #: ###-####
|