Inspections for the day of: Friday, December 7, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04550 Final12/7/201812/7/201812/7/2018 1:35:58 PMPPASS
system complete. stickers and labeling complete. approved plans on site.
ready for final. the site is open as a new build, so access is open all the time.
Thank you Phone #: ###-#### Inspection requested via web by Ryan King Ok final.
ELE18-04537 Permanent Service12/7/201812/7/201812/7/2018 12:37:32 PMPPASS
Rick Phone #: ###-#### Service located on the W side of 15th just before Hill Rd. p/s o/h rec ok
ELE18-04552 Final12/7/201812/7/201812/7/2018 12:15:37 PMPPASS
Solar install ready for inspection.
Approve plans are on site and all work has been completed according to plans.
Give me a call if you have any questions at ###-#### Phone #: ###-#### Inspection requested via web by Ryan King Ok final.
ELE18-03987 Electrical Rough-In12/6/201812/7/201812/7/2018 11:42:25 AMAPASS
Max Phone #: ###-#### Ok cover 3-2" pvc on S side of river at new structure.
ELE18-04110 Electrical Rough-In12/6/201812/7/201812/7/2018 10:28:27 AMAPASS
Richard Phone #: ###-#### Ok cover garage. Grounds at oultet locations are pigtailed. Fees are correct.
ELE18-04454 Final12/6/201812/7/201812/7/2018 10:27:49 AMAFAIL
###-####-Please call when on the way Phone #: ###-#### Inspection requested via web by Same Electric Table 680.9(A) requires an overhead service line not enclosed in conduit, to be a minimum of 10' horizontally outside the inside walls of a hottub or pool. If not, a height of 22.5' or more must be maintained from the top of the water line. In order for a final inspection, hottub location would need to changed, and a load calculation will need to be done as it is fed from a 90a main brkr.
ELE18-04658 Electrical Rough-In12/6/201812/7/201812/7/2018 9:32:49 AMAPASS
Contractor should be around all day. If not front door will be unlocked. Phone #: ###-#### Inspection requested via web by Dylan Pierce Ok cover kitchen.
ELE18-03591 Final12/6/201812/7/201812/7/2018 8:49:28 AMAPASS
garage code 2626 Phone #: ###-#### Inspection requested via web by Heath Thomas Ok final. Recess can above mstr tub.
ELE18-04635 Permanent Service12/6/201812/7/201812/6/2018 2:36:52 PMAPASS
Jerry Phone #: ###-#### p/s o/h n ok