BLD1053886
| INSP-Final Inspection | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | A | PASS |
|
|
smoke detectors all operational
|
BLD97-02311
| INSP-Final Inspection | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | A | PART |
|
|
SAYS HE HAS TALKED TO YOU - WILL SEE YOU 8: 30 MON install exit sign per approved plans
|
BLD97-02966
| INSP-Final Inspection | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | A | PASS |
|
|
all items from 406's c/n completed
|
BLD97-03041
| INSP-Final Inspection | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | A | PART |
|
|
approved plans not on site. business being conducted without c/o approved. replace key lock with panic/latching on side exit.
|
BLD97-03101
| INSP-Final Inspection | 12/8/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | P | FAIL |
|
|
RIVERVIEW PLAZA/ 3RD FLOOR penetrations to corridor have dampers, lacking detection. strobes not placed properly
|
BLD97-02678
| INSP-Final Inspection | 12/8/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | P | PASS |
|
|
STARBUCKS
|
BLD97-00508
| INSP-Sprinkler Rough-in/Hydro | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | P | PART |
|
|
hydro completed - passed. alarm valve leaking, must retest below check valve and underground
|
BLD97-01316
| INSP-Final Inspection | 12/5/1997 | 12/8/1997 | 12/8/1997 12:00:00 AM | P | PASS |
|
|
MED NOW all items on c/n complied
|