Inspections for the day of: Wednesday, December 8, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00012 INSP-Alarm Testing12/7/200412/8/200412/8/2004 12:00:00 AMAFAIL
Inspection stopped after testing initiating devices on the first and second floors. Third floor not looked at. Elevator recall and sprinkler flow not done nor duct detectors on the roof. Monitoring company did not receive trouble for loss of phone lines, a/c power or loss of batteries. Resubmittals required. See city approved plans for specific locations and deficiencies. 12/8/2004 2:58:42 PM
FIR04-00143 INSP-Alarm Testing12/7/200412/8/200412/8/2004 12:00:00 AMAPASS
fire alarm finaled 12/8/2004 2:49:23 PM
BLD04-01196 FIRE-Final Inspection12/7/200412/8/200412/8/2004 12:00:00 AMPPASS
Life safety finaled 12/8/2004 3:30:26 PM
BLD01-03114 FIRE-Final Inspection12/8/200412/8/200412/8/2004 12:00:00 AMPPASS
All items on the correction notice have been completed. Fire alarm was done today.