FIR03-00012
| INSP-Alarm Testing | 12/7/2004 | 12/8/2004 | 12/8/2004 12:00:00 AM | A | FAIL |
|
|
Inspection stopped after testing initiating devices on the first and second floors. Third floor not looked at. Elevator recall and sprinkler flow not done nor duct detectors on the roof. Monitoring company did not receive trouble for loss of phone lines, a/c power or loss of batteries. Resubmittals required. See city approved plans for specific locations and deficiencies. 12/8/2004 2:58:42 PM
|
FIR04-00143
| INSP-Alarm Testing | 12/7/2004 | 12/8/2004 | 12/8/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 12/8/2004 2:49:23 PM
|
BLD04-01196
| FIRE-Final Inspection | 12/7/2004 | 12/8/2004 | 12/8/2004 12:00:00 AM | P | PASS |
|
|
Life safety finaled 12/8/2004 3:30:26 PM
|
BLD01-03114
| FIRE-Final Inspection | 12/8/2004 | 12/8/2004 | 12/8/2004 12:00:00 AM | P | PASS |
|
|
All items on the correction notice have been completed. Fire alarm was done today.
|