ELE05-04426
| Electrical Rough-In | 12/8/2005 | 12/8/2005 | 12/8/2005 4:28:57 PM | P | PASS |
|
|
rough in for new walls; Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to cover walls only
|
ELE05-03999
| Electrical Rough-In | 12/8/2005 | 12/8/2005 | 12/8/2005 4:26:27 PM | P | PASS |
|
|
Rough in inspection Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson met elect, he will strap exst cnd, ric walls and clg ok
|
ELE05-04308
| Final | 12/8/2005 | 12/8/2005 | 12/8/2005 4:02:30 PM | P | CANC |
|
|
FINAL INSPECTION, JEFF WILL BE ON SITE; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see p/s and ok to final
|
ELE05-04308
| Permanent Service | 12/8/2005 | 12/8/2005 | 12/8/2005 4:01:43 PM | P | PASS |
|
|
FINAL INSPECTION, JEFF WILL BE ON SITE; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g n ok, ok to final
|
ELE05-04429
| Permanent Service | 12/8/2005 | 12/8/2005 | 12/8/2005 1:24:27 PM | P | PASS |
|
|
Please call prior to inspection mitch ###-#### p/s u/g reconnect ok
|
ELE05-04430
| Temporary Service | 12/8/2005 | 12/8/2005 | 12/8/2005 12:50:14 PM | P | FAIL |
|
|
###-#### - jean Note: please call 1/2 hr for location called contr, left corr notice, 408.4 circuit directory shall be provided, 310.13 shall use wire suitable for direct burial
|
ELE05-04323
| Electrical Rough-In | 12/7/2005 | 12/8/2005 | 12/8/2005 11:48:20 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/7/2005 at 3:25:11 PM. Contact: ###-####. left corr notice, met elect, 210.62 showroom recpts shall be installed
|
ELE05-04383
| Temporary Service | 12/8/2005 | 12/8/2005 | 12/8/2005 10:13:20 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 12/8/2005 at 7:08:39 AM. Contact: ###-####. couldn't find, wrong address on pole, no job id sticker, called contr
|
ELE05-02788
| Final | 12/7/2005 | 12/8/2005 | 12/8/2005 9:59:40 AM | A | FAIL |
|
|
TOBY; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, left corr notice, 210.8(A)(7)laundry room recpts shall be gfci protected, 210.8(A)(1) bathroom recpts shall be gfci protected, 110.3(A) outside stove shall be acceptable only if approved
|
ELE05-03779
| Final | 12/7/2005 | 12/8/2005 | 12/8/2005 9:28:23 AM | A | PASS |
|
|
jean; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles need service strap, told contr, ok to final
|
ELE05-01814
| Conference | 12/7/2005 | 12/8/2005 | 12/8/2005 9:27:25 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 12/7/2005 at 3:26:58 PM. Contact: ###-####.
|
ELE05-04232
| Rough-In Permanent Service | 12/7/2005 | 12/8/2005 | 12/8/2005 8:54:42 AM | A | PASS |
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy p/s from exst meter pak, n, ok
|
ELE05-01814
| Conference | 12/8/2005 | 12/8/2005 | 12/8/2005 12:00:00 AM | A | DONE |
|
|
review bkr for elev
|
ELE05-04232
| Final | 12/7/2005 | 12/8/2005 | 12/7/2005 2:11:01 PM | A | CANC |
|
|
DAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|