Inspections for the day of: Friday, December 8, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00384 FIRE-Final Inspection12/7/200612/8/200612/11/2006 3:29:25 PMAFAIL
Fire life safety final pending final of the project related fire alarm permit, also need to provide a current annual inspection for the existing sprinkler system as indicated in fire code review notes.
FIR06-00845 INSP-Final Inspection12/8/200612/8/200612/8/2006 4:13:32 PMPPASS
Fire sprinkler work is acceptable, one correction made while on site, inspection passed.
BLD06-01582 FIRE-Final Inspection12/7/200612/8/200612/8/2006 4:12:10 PMPPASS
Fire life safety inspection is satisfactory.
BLD06-00981 FIRE-Final Inspection12/7/200612/8/200612/8/2006 4:11:19 PMPPASS
Fire life safety final inspection passed.
FIR06-00270 INSP-Final Inspection12/6/200612/8/200612/8/2006 4:07:32 PMPFAIL
Intermittent operation of the flow switch must be repaired prior to alarm final, need to provide map at the panel as discussed, SD at the FACP to be tested at next inspection, all other items tested satisfactory.
FIR06-00894 INSP-Final Inspection12/6/200612/8/200612/8/2006 4:02:59 PMPPASS
Fire alarm work passed final inspection.
FIR06-00529 INSP-Final Inspection12/8/200612/8/200612/8/2006 4:02:08 PMPPASS
Fire alarm permit finaled.
FIR06-00768 INSP-Sprinkler Rough-in/Hydro12/5/200612/8/200612/8/2006 4:01:34 PMPPART
OH fire sprinkler is okay for cover as indicated on site. Noted drops at some locations are not yet complete, missing EQ bracing.
FIR06-00766 INSP-Conference12/7/200612/8/200612/8/2006 3:59:32 PMAPART
Inspection for a portion of the OH fire sprinkler installation as marked on plans is approved for cover.
FIR05-00772 INSP-Supply line flush12/7/200612/8/200612/8/2006 11:11:01 AMAFAIL
Inspection for the UG fire supply line flush was not completed due to lack of sufficient water flow. Noted the yard PIV was not operating correctly and is installed below allowable 36" height above grade.
FIR06-00809 INSP-Sprinkler Rough-in/Hydro12/7/200612/8/200612/8/2006 11:03:57 AMAPART
Overhead fire sprinkler at all drop ceilings within the tenant space are approved for cover with the exception of the womens restroom due to heads which exceed min. spacing as installed.