ELE08-01750
| ELE-Aging Inspection | 12/8/2008 | 12/8/2008 | 12/11/2008 10:17:56 AM | | DONE |
|
|
|
ESC08-00475
| General Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 3:34:41 PM | P | PASS |
|
|
ok
|
ELE08-03133
| Rough-In Permanent Service | 12/8/2008 | 12/8/2008 | 12/8/2008 3:33:54 PM | P | PASS |
|
|
Lynn Phone #: ###-#### r/i p/s u/g new ok
|
ELE08-02884
| Electrical Rough-In | 12/5/2008 | 12/8/2008 | 12/8/2008 2:34:09 PM | P | PASS |
|
|
Hi Bob, We need a ceiling cover inspection for most all of the ceiling. Blake will be onsite to show you the area''s, Ive listed his phone number for you. Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig ceilings ok
|
ELE08-02774
| Final | 12/8/2008 | 12/8/2008 | 12/8/2008 1:28:32 PM | P | PASS |
|
|
Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok no card
|
ESC08-00938
| General Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 12:36:50 PM | P | PASS |
|
|
site ok
|
ELE08-03034
| Final | 12/8/2008 | 12/8/2008 | 12/8/2008 12:35:22 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith see added r/i
|
ELE08-03034
| Electrical Rough-In | 12/8/2008 | 12/8/2008 | 12/8/2008 12:32:19 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith called corr. 300.11 shall provide support wires for cables that attach from structure to grid and shall ID them fixture wires do not provide support, 330.30 (A&B) shall secure cables within 12" of boxes, no cables shall lay on grid
|
ELE08-01873
| ELE-Aging Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 11:36:30 AM | | CANC |
|
|
|
ELE08-01873
| Final | 12/8/2008 | 12/8/2008 | 12/8/2008 11:36:24 AM | A | PASS |
|
|
|
ELE08-00261
| ELE-Aging Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 10:13:01 AM | | CANC |
|
|
|
ELE08-00261
| DOC - Permit Expired | 12/8/2008 | 12/8/2008 | 12/8/2008 10:12:53 AM | A | PASS |
|
|
|
ELE07-02945
| Electrical Rough-In | 12/5/2008 | 12/8/2008 | 12/8/2008 9:43:28 AM | A | FAIL |
|
|
wes - please call 1/2 hr prior Phone #: ###-#### box fill, 6" free length
|
ELE08-02642
| Electrical Rough-In | 12/5/2008 | 12/8/2008 | 12/8/2008 9:40:16 AM | A | FAIL |
|
|
george Phone #: ###-#### met contr. BCC 4-05-32 (nec 410.62 (C) needs cord cap and recepts for lights, 500.4 needs documentation for hazardous area (wood working), 250.30 grounding for seperately derived systems, 250.32 building suppied by outside feeder, 225.30,31,32 outside feeder (more than one building, 400.10 needs kellum grips for cords at cord caps,250.90 bonding of sevice, 314.3 metallic raceway in non-metallic box, note needs to attach bld to ele, all equip at site for label and listing 7 working days, may need extension
|
ELE08-02642
| Final | 12/5/2008 | 12/8/2008 | 12/8/2008 9:30:23 AM | A | FAIL |
|
|
george Phone #: ###-#### not ready
|