Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01750 ELE-Aging Inspection12/8/200812/8/200812/11/2008 10:17:56 AM DONE
ESC08-00475 General Inspection12/8/200812/8/200812/8/2008 3:34:41 PMPPASS
ok
ELE08-03133 Rough-In Permanent Service12/8/200812/8/200812/8/2008 3:33:54 PMPPASS
Lynn Phone #: ###-#### r/i p/s u/g new ok
ELE08-02884 Electrical Rough-In12/5/200812/8/200812/8/2008 2:34:09 PMPPASS
Hi Bob,
We need a ceiling cover inspection for most all of the ceiling. Blake will be onsite to show you the area''s, Ive listed his phone number for you.
Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig
ceilings ok
ELE08-02774 Final12/8/200812/8/200812/8/2008 1:28:32 PMPPASS
Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok no card
ESC08-00938 General Inspection12/8/200812/8/200812/8/2008 12:36:50 PMPPASS
site ok
ELE08-03034 Final12/8/200812/8/200812/8/2008 12:35:22 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Kathy Smith see added r/i
ELE08-03034 Electrical Rough-In12/8/200812/8/200812/8/2008 12:32:19 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Kathy Smith called corr. 300.11 shall provide support wires for cables that attach from structure to grid and shall ID them fixture wires do not provide support, 330.30 (A&B) shall secure cables within 12" of boxes, no cables shall lay on grid
ELE08-01873 ELE-Aging Inspection12/8/200812/8/200812/8/2008 11:36:30 AM CANC
ELE08-01873 Final12/8/200812/8/200812/8/2008 11:36:24 AMAPASS
ELE08-00261 ELE-Aging Inspection12/8/200812/8/200812/8/2008 10:13:01 AM CANC
ELE08-00261 DOC - Permit Expired12/8/200812/8/200812/8/2008 10:12:53 AMAPASS
ELE07-02945 Electrical Rough-In12/5/200812/8/200812/8/2008 9:43:28 AMAFAIL
wes - please call 1/2 hr prior Phone #: ###-#### box fill, 6" free length
ELE08-02642 Electrical Rough-In12/5/200812/8/200812/8/2008 9:40:16 AMAFAIL
george Phone #: ###-#### met contr. BCC 4-05-32 (nec 410.62 (C) needs cord cap and recepts for lights, 500.4 needs documentation for hazardous area (wood working), 250.30 grounding for seperately derived systems, 250.32 building suppied by outside feeder, 225.30,31,32 outside feeder (more than one building, 400.10 needs kellum grips for cords at cord caps,250.90 bonding of sevice, 314.3 metallic raceway in non-metallic box, note needs to attach bld to ele, all equip at site for label and listing 7 working days, may need extension
ELE08-02642 Final12/5/200812/8/200812/8/2008 9:30:23 AMAFAIL
george Phone #: ###-#### not ready