BLD08-00508
| FIRE-Conference | 12/8/2008 | 12/8/2008 | 12/8/2008 5:10:53 PM | P | NR |
|
|
Reed Phone#: ###-####
|
BLD08-01001
| FIRE-Final Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 5:10:29 PM | P | PASS |
|
|
See permit activities completed 7/03/08.
|
FIR07-00495
| INSP-Final Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 5:06:05 PM | P | PART |
|
|
Okay for final when ceilings are finished.
|
FIR08-00712
| INSP-Conference | 12/8/2008 | 12/8/2008 | 12/8/2008 5:05:31 PM | P | DONE |
|
|
Regarding site inspection schedule.
|
BLD08-02125
| FIRE-Final Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 5:04:50 PM | P | FAIL |
|
|
Need to repair one exit sign/EM light, provide certification tags for the two PFE's, lower mounting height at one fire extinguisher, remove non-illuminated exit sign at the north door, post tactile signs as discussed per plan review documents.
|
FIR07-00515
| INSP-Conference | 12/8/2008 | 12/8/2008 | 12/8/2008 12:21:27 PM | P | DONE |
|
|
Conversation with contractor regarding PIV location per NFPA 13 8.15.1.1.1.1 and 8.15.1.3 also 8.14.7.1 and IFC 903.3.1.2.1.
|
FIR08-00756
| INSP-Final Inspection | 12/8/2008 | 12/8/2008 | 12/8/2008 12:13:21 PM | A | NR |
|
|
Project is not ready for final at this time.
|
BLD08-01092
| FIRE-Final Inspection | 12/5/2008 | 12/8/2008 | 12/8/2008 12:03:25 PM | A | PASS |
|
|
Scope of work passed fire life safety inspection.
|
BLD08-02493
| FIRE-Final Inspection | 12/5/2008 | 12/8/2008 | 12/8/2008 11:42:48 AM | A | FAIL |
|
|
Exit signs at several locations are not functional and in need of repair, need to remove the hasp and padlock at the back exit door, post max. occupant load sign with the correct number per review documents, provide current certification tags for the two fire extinguishers and post as discussed, repair one EM light at the pool table room. See permit documents for details.
|
BLD08-01434
| FIRE-Conference | 12/8/2008 | 12/8/2008 | 12/8/2008 10:43:07 AM | A | DONE |
|
|
Regarding project related fire alarm permit.
|