Inspections for the day of: Monday, December 8, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01007 FIRE-Final Inspection12/5/200812/8/200812/12/2008 3:16:58 PMACANC
Waiting on confermation that an agreement has been reached with the fire dept.
BLD07-02644 FIRE-Conference12/8/200812/8/200812/8/2008 4:20:14 PMPDONE
I went over life safety requirements for this project. It appears per the fire review comments that a fire hydrant was to be installed out front and fire sprinklers/alarm systems were to be installed as well. These items have not been installed. Scott and Sam have been contacted.
BLD08-02329 FIRE-Final Inspection12/8/200812/8/200812/8/2008 4:18:11 PMPFAIL
Sprinkler protection is required under the new overhead doors. All other items are ok.
FIR08-00006 INSP-Final Inspection12/5/200812/8/200812/8/2008 3:27:04 PMPFAIL
This inspection turned into a first floor walk through/conference. All of the first floor wing smoke detectors are overspaced, a smoke detector in the common are needs to be relocated closer to the double doors to the wing and visuals are overspaced. Locations are marked on the plans. No testing was performed.
FIR08-00798 INSP-Final Inspection12/8/200812/8/200812/8/2008 1:37:06 PMPPASS
Permit finaled
FIR08-00726 INSP-Final Inspection12/8/200812/8/200812/8/2008 1:34:31 PMPPASS
permit finaled
FIR08-00755 INSP-Sprinkler Rough-in/Hydro12/5/200812/8/200812/8/2008 11:58:35 AMAPASS
The underground supply piping is ok to cover but the piping layout does not match the city approved print. The changes will need to be reflected on the overhead piping layout and hydraulic calculations prior to final inspection.
BLD08-02242 FIRE-Final Inspection12/5/200812/8/200812/8/2008 11:06:35 AMAFAIL
Still need the dead bolt removed from the gate to the basement and a "Door to remain unlocked while the building is occupied" sticker at the exit as per the original correction notice.
FIR08-00798 INSP-Sprinkler Rough-in/Hydro12/5/200812/8/200812/8/2008 10:21:19 AMAPASS
Rough-in inspection passed.
FIR08-00726 INSP-Sprinkler Rough-in/Hydro12/5/200812/8/200812/8/2008 10:19:54 AMAPASS
Rough-in inspection passed
FIR08-00626 INSP-Supply line flush12/5/200812/8/200812/8/2008 10:17:44 AMAPART
The flush for the underground supply line passed but the supply line for the remote FDC has not been flushed as required.