Inspections for the day of: Tuesday, December 8, 2009.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00530 FIR-Aging Inspection12/8/200912/8/200912/16/2009 3:11:46 PM NR
Work is in progress as based on the last conversation I had with Guy.
FIR09-00676 INSP-Sprinkler Rough-in12/8/200912/8/200912/8/2009 3:20:05 PMPPASS
Sprinkler piping is ok to cover.
BLD09-00945 FIRE-Final Inspection12/7/200912/8/200912/8/2009 2:23:41 PMAFAIL
This inspection was for phase 2. The insulation at the roof deck needs repaired. The existing "access controled egress" lock on the door to the lobby needs to meet the requirements of chapter 10 of the IFC. An existing duct smoke detector has been removed from a hvac unit and will need to be re-installed and tested. The existing fire alarm system will need to be tested for functionality as well. The ADA compliant door hardware has not been installed on both doors for the short corridor next to the electrical room as shown to be done on the city approved plans. I spoke to Chris with HC Company about the fire alarm/duct smoke detector and the "access controled egress door" via a phone conversation.
BLD09-02001 FIRE-Final Inspection12/7/200912/8/200912/8/2009 1:12:33 PMAFAIL
Provide a tagged fire extinguisher as discussed. All other items wil be ok.
BLD09-01856 FIRE-Final Inspection12/7/200912/8/200912/7/2009 3:07:25 PMAPASS
life safety passed