ELE10-01913
| ELE-Aging Inspection | 12/8/2010 | 12/8/2010 | 12/16/2010 3:33:47 PM | | DONE |
|
|
wsuc
|
ELE10-00692
| ELE-Aging Inspection | 12/8/2010 | 12/8/2010 | 12/14/2010 1:21:37 PM | | DONE |
|
|
wsuc
|
ELE10-01175
| ELE-Aging Inspection | 12/8/2010 | 12/8/2010 | 12/14/2010 1:21:15 PM | | CANC |
|
|
|
ELE10-02187
| Final | 12/8/2010 | 12/8/2010 | 12/8/2010 2:19:12 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jim Snodgrass ok no card
|
ELE10-02402
| Final | 12/8/2010 | 12/8/2010 | 12/8/2010 2:18:42 PM | P | FAIL |
|
|
Two little classrooms at north end of school. Phone #: ###-#### >> Inspection requested via web by Jim Snodgrass
corr 210.8(B) (5)
|
ELE10-02665
| Permanent Service | 12/6/2010 | 12/8/2010 | 12/8/2010 11:51:53 AM | A | FAIL |
|
|
roger Phone #: ###-#### panel set too high 240.24, 200.2(B), 250.24(A) terninate EGC at neutral bus, 250-66 needs #4 to bind nipple for 200 amp p/s
|
ELE10-02012
| Final | 12/7/2010 | 12/8/2010 | 12/8/2010 11:41:24 AM | A | FAIL |
|
|
Basement only key in box---Clay Phone #: ###-#### called open grds 4 recepts also loose recepts
|
ELE10-02670
| Permanent Service | 12/7/2010 | 12/8/2010 | 12/8/2010 11:39:20 AM | A | FAIL |
|
|
inspection for electrical connection of mobile home Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called needs to move gas meter for required clearence
|