ELE11-02417
| Electrical Rough-In | 12/7/2011 | 12/8/2011 | 12/8/2011 2:06:18 PM | P | FAIL |
|
|
side door garage unlocked. inspect kitchen, utility,pantry, entry wiring. Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, left message, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm shall be stapled within 12" of box, 110.12(B) there shall be no broken boxes (open ko), 210.52(A) shall provide outlet in 2' wall at kitchen, shall provide light box and ground metal boxes, BCC no violations shall be retained- 1 1/4" flex for heater, shall change room count on permit to 6 rooms
|
ELE11-02441
| Final | 12/7/2011 | 12/8/2011 | 12/8/2011 10:26:33 AM | A | PASS |
|
|
Please call ###-#### for information to gain access. Phone #: ###-#### >> Inspection requested via web by Dave Koeppen ok final
|
ELE11-02532
| Final | 12/7/2011 | 12/8/2011 | 12/8/2011 9:37:33 AM | A | PASS |
|
|
LYNN Phone #: ###-#### ok final, signed card
|
ELE11-02749
| Rough-In Permanent Service | 12/7/2011 | 12/8/2011 | 12/8/2011 8:43:00 AM | A | PASS |
|
|
Correction made to flex run. UL stickers are on top of the VFD''S. Thanks, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell corrections made, ri ok, p/s u/g n ok
|
ELE11-01792
| Final | 12/7/2011 | 12/8/2011 | 12/8/2011 8:20:43 AM | A | FAIL |
|
|
East half of building, Temporary occupancy Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld met contractor, left correction notice, NEC 408.4 shall provide circuit directories, BCC 4-05-33(A)(B) shall provide listing for led lights, tv pole assembly, and vault door,rest ok, check electrical room
|