Inspections for the day of: Thursday, December 8, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02417 Electrical Rough-In12/7/201112/8/201112/8/2011 2:06:18 PMPFAIL
side door garage unlocked. inspect kitchen, utility,pantry, entry wiring. Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, left message, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm shall be stapled within 12" of box, 110.12(B) there shall be no broken boxes (open ko), 210.52(A) shall provide outlet in 2' wall at kitchen, shall provide light box and ground metal boxes, BCC no violations shall be retained- 1 1/4" flex for heater, shall change room count on permit to 6 rooms
ELE11-02441 Final12/7/201112/8/201112/8/2011 10:26:33 AMAPASS
Please call ###-#### for information to gain access. Phone #: ###-#### >> Inspection requested via web by Dave Koeppen ok final
ELE11-02532 Final12/7/201112/8/201112/8/2011 9:37:33 AMAPASS
LYNN Phone #: ###-#### ok final, signed card
ELE11-02749 Rough-In Permanent Service12/7/201112/8/201112/8/2011 8:43:00 AMAPASS
Correction made to flex run. UL stickers are on top of the VFD''S. Thanks, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell corrections made, ri ok, p/s u/g n ok
ELE11-01792 Final12/7/201112/8/201112/8/2011 8:20:43 AMAFAIL
East half of building, Temporary occupancy Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld met contractor, left correction notice, NEC 408.4 shall provide circuit directories, BCC 4-05-33(A)(B) shall provide listing for led lights, tv pole assembly, and vault door,rest ok, check electrical room