Inspections for the day of: Thursday, December 8, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00263 INSP-Final Inspection12/6/201112/8/201112/12/2011 8:55:22 AMACANC
Rescheduled for 12/12/2011
FIR11-00610 INSP-Sprinkler Rough-in/Hydro12/8/201112/8/201112/8/2011 3:37:16 PMPPASS
Rough-in passed. Sprinkler piping can be covered.
BLD11-01251 FIRE-Final Inspection12/7/201112/8/201112/8/2011 3:03:19 PMPFAIL
This inspection was for the east side remodeled area only. The two exit discharge lights need to be repaired. Also a fire alarm sytem is shown to be installed but has not been. It appears to be only there to monitor the duct smoke detectors. I told the contractor that the remote annunciators as installed are ok if the fire alarm panel is installed. If it is not installed then the correct remote annunciators need to be installed. The duct smoke detectors will need to be tested when a decision has been made.
FIR11-00543 INSP-Sprinkler Rough-in12/8/201112/8/201112/8/2011 12:50:02 PMPPASS
The sprinkler piping in rooms 193, 194, 195 and 196 is ok to cover. I also spoke to Scott with Jacobsen Construction about inspections prior to covering.
FIR11-00579 INSP-Sprinkler Rough-in12/8/201112/8/201112/8/2011 12:43:36 PMPPASS
The second floor office sprinkler piping can be covered.
BLD11-02516 FIRE-Final Inspection12/8/201112/8/201112/8/2011 12:12:18 PMAPASS
life safety passed. I let Jr. know that the keyed dead bolt to the gun room will need to be single action on the egress side.
FIR11-00374 INSP-Sprinkler Rough-in12/7/201112/8/201112/8/2011 11:12:52 AMAPASS
The second floor office sprinkler piping is ok to cover.
BLD11-01835 FIRE-Final Inspection12/7/201112/8/201112/8/2011 10:27:06 AMAFAIL
Resubmitt plans showing the actual floor layout, mount and tag fire extinguisher as marked on the plans, provide approved door hardware as marked on the plans, provide missing exit signs as marked on the plans and repair the emergency light as marked on the plans.
BLD11-02349 FIRE-Final Inspection12/7/201112/8/201112/8/2011 9:20:05 AMAPASS
life safety passed
FIR11-00600 INSP-Final Inspection12/7/201112/8/201112/8/2011 9:19:48 AMAPASS
permit finaled
FIR11-00541 INSP-Sprinkler Rough-in12/7/201112/8/201112/8/2011 9:02:13 AMAPASS
Sprinkler piping can be covered but as-builts showing the actual supply piping layout is required prior to a final sign off. The piping arrangement shown is not even close.
FIR11-00609 INSP-Final Inspection12/7/201112/8/201112/8/2011 7:39:26 AMAPASS
Permit finaled