Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03945 Temporary Service12/8/201512/8/201512/8/2015 2:47:38 PMPPASS
Temp pole Phone #: ###-#### Inspection requested via web by TOM BICANDI
t/s u/g n ok
ELE15-00323 Final12/6/201512/8/201512/8/2015 2:19:28 PMPPASS
final on led poleheads Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
ELE15-00323 Electrical Rough-In12/8/201512/8/201512/8/2015 1:54:46 PMPPASS
final on led poleheads Phone #: ###-#### Inspection requested via web by Tim Dunlop UL listing confirmed rough in ok
ELE15-03389 Final12/8/201512/8/201512/8/2015 1:50:28 PMPPASS
Please re-inspect final Phone #: ###-#### Inspection requested via web by David Mackey Final ok
ELE15-03389 Permanent Service12/8/201512/8/201512/8/2015 1:47:23 PMPPASS
Please re-inspect final Phone #: ###-#### Inspection requested via web by David Mackey p/s o/h n ok
ELE15-03911 Permanent Service12/4/201512/8/201512/8/2015 1:14:57 PMPPASS
McMillan and Maple Grove nearest cross streets Phone #: ###-#### Inspection requested via web by Dean Gernaat
p/s u/g rec ok
ELE15-03944 Temporary Service12/8/201512/8/201512/8/2015 12:40:47 PMPPASS
Please call Jeff If you have any questions. Thanks Phone #: ###-#### Inspection requested via web by Brandon Blackham t/s u/g n ok
ELE15-03941 Temporary Service12/8/201512/8/201512/8/2015 12:00:32 PMPPASS
READY NOW Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE15-03927 Rough-In Permanent Service12/8/201512/8/201512/8/2015 11:07:04 AMAFAIL
Please call for access code. Phone #: ###-#### Inspection requested via web by David Nelson
110.12(B)- 12-2 under panel damaged repair or replace.
210.12(A)- Outlets located in bedrooms shall have AFCI protection.
200.7(C)(1)- White conductors used for ungrounded conductors shall be identified other than white.
334.23- NM cable located with in 7' of attic access shall be protected be runners.
Back bedroom area not damaged but homeruns replaced.
ELE15-03927 Permanent Service12/8/201512/8/201512/8/2015 11:06:40 AMPPASS
Please call for access code. Phone #: ###-#### Inspection requested via web by David Nelson p/s o/h rec ok
ELE15-01111 Electrical Rough-In12/7/201512/8/201512/8/2015 10:00:39 AMAPASS
We need an underground inspection, please. Call Danny prior to arrival. Phone #: ###-#### Inspection requested via web by Stacie Tasker Underground to 15 central pole locations. Rough in ok cover
ELE15-03769 Rough-In Permanent Service12/7/201512/8/201512/8/2015 9:29:57 AMAPASS
Tim Phone #: ###-#### Service change ready at time of inspection. #2 SER shall be fused down to 80 amp as per 310.15(B)(7). p/s o/h rec ok
ELE15-02812 Final12/7/201512/8/201512/8/2015 8:45:03 AMAPASS
SHAWN CASE Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE15-02812 Electrical Rough-In12/8/201512/8/201512/8/2015 8:44:49 AMPPASS
SHAWN CASE Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid rough in ok cover