Inspections for the day of: Tuesday, December 8, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02333 FIRE-Final Inspection12/8/201512/8/201512/8/2015 2:56:39 PMPFAIL
Inspection was actually for a conference. I spoke to Dave about minimum clearances between the covered car ports. 20'-0" in the minimum on the east/west street and 26'-0" on the north/south street due to a fire hydrant. Referenc IFC appendix D
FIR15-00724 INSP-Sprinkler Rough-in12/8/201512/8/201512/8/2015 2:05:23 PMPPASS
See the city approved plans for hard lid areas where the piping is ok to cover. I noted that branch line restraints will be required for all new branchlines that require it.
FIR15-00719 INSP-Sprinkler Rough-in/Hydro12/7/201512/8/201512/8/2015 2:03:53 PMPPART
Overhead hydro of the first floor passed. The overhead hydro of the second floor failed twice.
FIR15-00556 INSP-Supply line flush12/7/201512/8/201512/8/2015 11:56:58 AMAPASS
Underground flush passed