NAF15-00025
| INSP-Sprinkler Rough-in/Hydro | 12/8/2015 | 12/8/2015 | 12/8/2015 8:32:25 AM | P | PASS |
|
|
Hydrostatic test completed satisfactory 12/7/15 (reading at 2:10pm 212 psi, again at 4:14pm 212psi) Rough in inspection completed satisfactory, ok to cover. **To be verified at final** two dry pendants in cooler, 4 dry sidewalls at entrances and one regular sidewall in electrical room. Stubs were present at roughin . Also to be completed riser accessories (FDC, main drain etc)
|