Inspections for the day of: Friday, December 8, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03784 Electrical Rough-In12/7/201712/8/201712/8/2017 2:45:22 PMPPART
Can lights above hard lid ceilings Phone #: ###-#### Inspection requested via web by Debby Pierce
Bathroom lids not ready, shall frame in accesses for junction boxes located above hardlids. Other drop lids rough in ok cover
MIS17-00380 ELE-Final11/8/201712/8/201712/8/2017 1:45:00 PMAFAIL
Revisit Buffalo Wild Wings about flexible cords installed above grid from panel off kitchen. Contact Jen Davis (Training General Manager).
E-mail- 671@buffalowildwings.com
Permit search shows not activity for ELE permit covering repair of violations. Hand delivered correction notice of violation to Jen Davis (Training General Manager). She stated she informed General Contractor on 11-8-17 of violation and will inform of this notice. Emailed what future actions could take place explaining 25 and 5 day notice of violation procedures.
ELE17-03811 Electrical Rough-In12/8/201712/8/201712/8/2017 1:11:57 PMPFAIL
Structural inspector called concerning notes from electrical inspection. Last sentence refers to general contractor stating he had conversation with 375 Eric Story about allowing violations with access and work clearences. Eric Story denies having this conversation and would not give anyone permission to do an install not compliant with current NEC.
ELE17-04123 Final12/7/201712/8/201712/8/2017 11:10:49 AMAPASS
Lighting rough-in and install of owner supplied fixtures
call Lance 30 minutes for notice and excess to space
208 703 2035
Phone #: ###-#### Inspection requested via web by David Feller
Final ok
ELE17-04123 Electrical Rough-In12/7/201712/8/201712/8/2017 11:10:23 AMAPASS
Lighting rough-in and install of owner supplied fixtures
call Lance 30 minutes for notice and excess to space
208 703 2035
Phone #: ###-#### Inspection requested via web by David Feller
MC fished between light openings and luminaires installed. rough in ok
ELE17-02862 Electrical Rough-In12/7/201712/8/201712/8/2017 10:19:39 AMAPASS
PT deck concrete pour call craig Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed the use of NM cable for floors 1 thru 5 which are wood construction, type 3, 4, and 5 construction NM cables permitted as long as behind 15 minute barrier or greater and not above suspended ceilings.
PT deck east 1/2 pour rough in ok cover.
ELE16-04017 Permanent Service12/7/201712/8/201712/8/2017 9:27:45 AMAPASS
Available Fault current at MC 62,561 Inspection requested via web by Debby Pierce p/s u/g n ok
ELE17-03709 Rough-In Permanent Service12/8/201712/8/201712/8/2017 8:55:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Rough in ok cover p/s u/g n ok
ELE17-03710 Rough-In Permanent Service12/8/201712/8/201712/8/2017 8:54:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Rough in ok cover p/s u/g n ok