Inspections for the day of: Friday, December 8, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00459 INSP-Sprinkler Rough-in12/8/201712/8/201712/8/2017 2:37:22 PMPCANC
Underground not complete, inspection request will be rescheduled for a later date, this request is cancelled.
FIR17-00452 INSP-Sprinkler Rough-in12/7/201712/8/201712/8/2017 2:37:10 PMPCANC
Underground not complete, inspection request will be rescheduled for a later date, this request is cancelled.
FIR17-00483 INSP-Sprinkler Rough-in12/7/201712/8/201712/8/2017 2:36:58 PMPCANC
Underground not complete, inspection request will be rescheduled for a later date, this request is cancelled.
FIR17-00446 INSP-Sprinkler Rough-in12/7/201712/8/201712/8/2017 2:36:13 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00447 INSP-Sprinkler Rough-in12/7/201712/8/201712/8/2017 2:35:56 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00448 INSP-Sprinkler Rough-in12/7/201712/8/201712/8/2017 2:35:34 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR17-00393 INSP-Sprinkler Rough-in/Hydro12/7/201712/8/201712/8/2017 2:20:53 PMPDONE
Overhead hydrostatic test witnessed and complete, no pressure loss observed at riser gauge.
FIR17-00701 INSP-Sprinkler Rough-in12/8/201712/8/201712/8/2017 1:56:37 PMPPASS
Rouh to cover inspection for area of work complete, approved for cover. In tenant space there are two different types of heads in the same area, Viking Standard response GB 155 degree and Reliable Model G heads, model G heads need to be changed to glass bulb Viking heads. Head change will be verified at final inspection.
FIR17-00701 INSP-Final Inspection12/8/201712/8/201712/8/2017 1:52:24 PMPCANC
Tenant space not ready for final inspection, this inspection request is going to be changed to a rough in inspection.
NAF17-00067 INSP-Final12/7/201712/8/201712/8/2017 11:27:14 AMAFAIL
Gas valve did not automatically shut down with west side hood fire suppression system activation, valve did shut gas off on east side hood suppression system activation. System will need to be retested for energy source isolation during hood activation.
NAF17-00076 INSP-Final12/1/201712/8/201712/8/2017 11:25:04 AMADONE
Final fire alarm inspection for scope of work passed/compete
BLD17-03418 FIRE-Final Inspection12/7/201712/8/201712/8/2017 11:24:01 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work passed/complete.
FIR17-00709 INSP-Final Inspection12/7/201712/8/201712/8/2017 9:43:32 AMAPART
Partial final inspection complete for fire sprinkler modifications in scope of work. Modifications have been made to the fire sprinkler system that was not done by Tribal Fire, demo work has also ben done by someone other than Tribal Fire.