Inspections for the day of: Thursday, December 9, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03540 Rough-In Permanent Service12/9/200412/9/200412/9/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/9/2004 at 7:21:04 AM. Contact: ###-####. called needs additional outlet 550.32(D) p/s o/h rec. ok 12/9/2004 10:17:00 AM
ELE04-03853 Rough-In Permanent Service12/8/200412/9/200412/9/2004 12:00:00 AMANR
Steve; Phone #: ###-#### Internet Inspection Request from: Jan Rice nr called
12/9/2004 8:42:19 AM
ELE04-03858 Final12/8/200412/9/200412/9/2004 12:00:00 AMAFAIL
louis ###-#### cor. posted called 250.66 needs #4 bond to bushing, 110.3 use manufactures breakers only, 11.2&3 spa not listed for use in US , its a canadian spa note this should of been a r/io p/s not final 12/9/2004 9:39:13 AM
ELE04-02193 Final12/9/200412/9/200412/9/2004 12:00:00 AMPPASS
shell final; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok no card 12/9/2004 1:19:12 PM
ELE04-03507 Electrical Rough-In12/9/200412/9/200412/9/2004 12:00:00 AMPFAIL
approval for ceiling cover in areas with grid ceiling; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. posted called, 300.11(ABC) raceways or cables shall not support cables or raceways, if wires are used do as code noted states 314.23(D) shall support boxes, 110.26(F)(1) provide clearence for all panels (panels above ceiling grid, all wiring shall meet 517 for patient care area 800.2,760.2,725.2 remove abandoned cables, 800.5&6, 760.5&6, 725.5&6 support, protect, and install as code noted states B C C no violations retained 12/9/2004 2:16:12 PM
ELE04-03458 Final12/9/200412/9/200412/9/2004 12:00:00 AMPPASS
CONTACT: CHRIS CARMINE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok card signed 12/9/2004 3:14:09 PM
ELE04-03671 Electrical Rough-In12/9/200412/9/200412/9/2004 12:00:00 AMPPART
concrete floor inspection please///allan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok u/g and boxes 12/9/2004 11:59:29 AM