FIR09-00193
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/10/2009 5:11:54 PM | P | PART |
|
|
Partial testing of the relocated duct detector housings completed today, noted RTU 26 detector failed to report to the panel, manometer testing completed okay for the units tested.
|
FIR09-00471
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:54:15 PM | P | PART |
|
|
Notification and new manual pull stations per the scope of work indicated passed inspection, remainder of work to be tested at next visit per discussion.
|
BLD09-02136
| FIRE-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:41:06 PM | P | FAIL |
|
|
Missing max. occupant load sign, provide one "K class" extinguisher for the kitchen, post suite address numbers, remove surface mounted hasp locks at three locations, provide certification of a current annual inspection for the fire sprinkler system, the type one hood suppression system needs modification to properly cover new appliance layout (permit required for modifications). See list of general conditions on permit documents for details.
|
FIR09-00639
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:36:48 PM | P | PASS |
|
|
Fire alarm permit final approved.
|
FIR09-00637
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:36:18 PM | P | PASS |
|
|
Fire alarm modifications passed functional test, permit finaled.
|
FIR09-00685
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:35:30 PM | P | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
BLD09-01689
| FIRE-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:34:35 PM | P | NR |
|
|
Contact Phone #: ###-####
|
FIR09-00627
| INSP-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 5:33:53 PM | P | FAIL |
|
|
Missing signage and locks/seals at the control valves to the system piping, need escutcheon in place and the travel cap and tape/paper removed from the pendent head.
|
FIR09-00586
| INSP-Sprinkler Rough-in | 12/8/2009 | 12/9/2009 | 12/9/2009 5:30:07 PM | A | PART |
|
|
Overhead fire sprinkler modifications per the scope of work indicated passed rough-in inspection and are approved for cover. See notes on plans for locations okayed to date, noted two raised decks missing coverage underneath.
|