Inspections for the day of: Wednesday, December 9, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00193 INSP-Final Inspection12/9/200912/9/200912/10/2009 5:11:54 PMPPART
Partial testing of the relocated duct detector housings completed today, noted RTU 26 detector failed to report to the panel, manometer testing completed okay for the units tested.
FIR09-00471 INSP-Final Inspection12/9/200912/9/200912/9/2009 5:54:15 PMPPART
Notification and new manual pull stations per the scope of work indicated passed inspection, remainder of work to be tested at next visit per discussion.
BLD09-02136 FIRE-Final Inspection12/9/200912/9/200912/9/2009 5:41:06 PMPFAIL
Missing max. occupant load sign, provide one "K class" extinguisher for the kitchen, post suite address numbers, remove surface mounted hasp locks at three locations, provide certification of a current annual inspection for the fire sprinkler system, the type one hood suppression system needs modification to properly cover new appliance layout (permit required for modifications). See list of general conditions on permit documents for details.
FIR09-00639 INSP-Final Inspection12/9/200912/9/200912/9/2009 5:36:48 PMPPASS
Fire alarm permit final approved.
FIR09-00637 INSP-Final Inspection12/9/200912/9/200912/9/2009 5:36:18 PMPPASS
Fire alarm modifications passed functional test, permit finaled.
FIR09-00685 INSP-Final Inspection12/9/200912/9/200912/9/2009 5:35:30 PMPPASS
Fire alarm testing passed, permit finaled.
BLD09-01689 FIRE-Final Inspection12/9/200912/9/200912/9/2009 5:34:35 PMPNR
Contact Phone #: ###-####
FIR09-00627 INSP-Final Inspection12/9/200912/9/200912/9/2009 5:33:53 PMPFAIL
Missing signage and locks/seals at the control valves to the system piping, need escutcheon in place and the travel cap and tape/paper removed from the pendent head.
FIR09-00586 INSP-Sprinkler Rough-in12/8/200912/9/200912/9/2009 5:30:07 PMAPART
Overhead fire sprinkler modifications per the scope of work indicated passed rough-in inspection and are approved for cover. See notes on plans for locations okayed to date, noted two raised decks missing coverage underneath.