Inspections for the day of: Thursday, December 9, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00407 FIR-Aging Inspection12/9/201012/9/201012/16/2010 12:55:53 PM PASS
Permit has been finaled
FIR39-00014 FIR-Aging Inspection12/9/201012/9/201012/14/2010 2:32:02 PM PASS
Do not occupy sticker placed on front door. Owner came out and stated "Get off my lawn"!.
FIR10-00549 INSP-Final Inspection12/7/201012/9/201012/9/2010 3:10:15 PMAPASS
permit finaled
FIR10-00536 INSP-Final Inspection12/7/201012/9/201012/9/2010 3:08:17 PMAPASS
Permit finaled.
BLD10-02331 FIRE-Final Inspection12/8/201012/9/201012/9/2010 2:49:54 PMAPASS
life safety passed. The building inspector will cover the door hardware.
BLD07-01561 FIRE-Conference12/2/201012/9/201012/9/2010 12:27:30 PMADONE
Per Tammy things should be complete soon.
BLD10-00970 FIRE-Conference12/8/201012/9/201012/9/2010 12:22:41 PMADONE
Lance and I went over life safety requirements.
FIR10-00447 INSP-Final Inspection12/7/201012/9/201012/9/2010 10:32:04 AMAFAIL
A soffit has been installed against the south wall which is causing an obstruction. The pendant heads will not provide coverage beneath it. This obstruction was not shown on the approved sprinkler plans. Also the flow switch needs to be tested through an approved orfice. The approved plans show a bell on the new office but one has not been installed. Per Tim Frost this new flow switch can be wired into the existing bell on the existing house.