ELE11-02103
| Final | 12/9/2011 | 12/9/2011 | 12/9/2011 3:13:05 PM | P | PASS |
|
|
Inspect all of the Kitchen, Living Room, Front Room. I just realized I forgot to reinstall two lights on the garage after the siding was changed. Please inspect PM so I can have time to get those installed. Phone #: ###-#### >> Inspection requested via web by nathan palmer ok final
|
ELE11-02229
| Permanent Service | 12/8/2011 | 12/9/2011 | 12/9/2011 2:25:50 PM | P | PASS |
|
|
Toby Phone #: ###-#### >> Inspection requested via web by Sean DeLacy p/s u/g n ok NOTE; contractor shall verify available fault current from IPCO
|
ELE11-02554
| Electrical Rough-In | 12/8/2011 | 12/9/2011 | 12/9/2011 1:33:26 PM | P | FAIL |
|
|
don please call before going out- Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide 6" free conductor at box, 250.86 shall provide ground screw in metal boxes, 300.4(A)(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.16 shall not exceed box fill, 334.30 shall staple nm within 12" of box or314.17(C) shall staple nm within 8" if more than 1 nm enters box, BCC all make-up shall be done
|
ELE11-02772
| Permanent Service | 12/9/2011 | 12/9/2011 | 12/9/2011 12:47:52 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt talked about concrete encased electrode not being deep enough or ground rods, and to recall
|
ELE11-02767
| Temporary Service | 12/9/2011 | 12/9/2011 | 12/9/2011 10:25:22 AM | A | PASS |
|
|
THANKS, HAVE A GOOD WEEKEND! BOB Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE11-00639
| Final | 12/7/2011 | 12/9/2011 | 12/9/2011 10:01:35 AM | A | PASS |
|
|
Rocky Phone #: ###-#### ok final
|
ELE11-01792
| Final | 12/8/2011 | 12/9/2011 | 12/9/2011 8:42:13 AM | A | PART |
|
|
temporary occupancy UL listing has been found Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld east part done, left correction notice stating BCC4-05-33(A)(B) shall provide listing within 30 days for led lighting and tv stand or that further action will be taken such as removal of power from building, no card to sign for temp occ
|
ELE11-01515
| Electrical Rough-In | 12/7/2011 | 12/9/2011 | 12/9/2011 7:56:28 AM | A | NR |
|
|
Contact: Brian Giacomino - Partial final inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden still wiring, wanted pm inspection
|