ELE14-03328
| Permanent Service | 12/8/2014 | 12/9/2014 | 12/9/2014 2:45:05 PM | P | PASS |
|
|
Please Call Gerald @###-#### To Gain Access To The Residence. We made All The Corrections And its ready To Energize Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett p/s u/g rec ok
|
ELE14-03328
| Final | 12/9/2014 | 12/9/2014 | 12/9/2014 2:34:09 PM | P | PASS |
|
|
Please Call Gerald @###-#### To Gain Access To The Residence. We made All The Corrections And its ready To Energize Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Service reconnect Final ok
|
ELE14-03363
| Rough-In Permanent Service | 12/9/2014 | 12/9/2014 | 12/9/2014 1:49:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
GCE14-00172
| GCE-Final | 12/9/2014 | 12/9/2014 | 12/9/2014 12:59:27 PM | P | PASS |
|
|
Karl ###-#### Final ok
|
ELE14-03233
| Permanent Service | 12/9/2014 | 12/9/2014 | 12/9/2014 12:22:13 PM | P | PASS |
|
|
INSPECTION IS REQUESTED BY POWER COMPANY - PLEASE INSPECT THIS MORNING IF POSSIBLE. Phone #: ###-#### Inspection requested via web by PAUL PINNEY p/s o/h rec ok
|
ELE14-03233
| Final | 12/9/2014 | 12/9/2014 | 12/9/2014 12:21:56 PM | P | PASS |
|
|
INSPECTION IS REQUESTED BY POWER COMPANY - PLEASE INSPECT THIS MORNING IF POSSIBLE. Phone #: ###-#### Inspection requested via web by PAUL PINNEY Service reconnect final ok
|
ELE14-03380
| Electrical Rough-In | 12/8/2014 | 12/9/2014 | 12/9/2014 10:53:51 AM | A | PASS |
|
|
HP is Journeyman contact. Phone #: ###-#### Inspection requested via web by Tyler Bowen Exploritorium walls rough in ok cover
|
ELE14-02802
| Final | 12/8/2014 | 12/9/2014 | 12/9/2014 10:08:45 AM | A | PASS |
|
|
Inspection requested via web by HZ ZAHIC Final ok
|
ELE14-03253
| Final | 12/8/2014 | 12/9/2014 | 12/9/2014 9:31:29 AM | A | FAIL |
|
|
Spoke with owner would like to meet around 9 am tues morning. suzanne ###-#### for service upgrade add panel 200.7- Conductor marked as grounded conductor used as ungrounded conductor for water heater shall be other than white or green. 300.4- holes bored less than 1 1/4" from framing surface shall have nail plates to protect NM cable from damage above panel. 422.31(B)- Water heater shall have disconnecting means. Breaker lockout acceptable. Left correction noticeand called contractor
|
ELE14-03253
| Permanent Service | 12/9/2014 | 12/9/2014 | 12/9/2014 9:23:49 AM | P | PASS |
|
|
Spoke with owner would like to meet around 9 am tues morning. suzanne ###-#### for service upgrade add panel p/s u/g rec ok
|
ELE14-03378
| Electrical Rough-In | 12/8/2014 | 12/9/2014 | 12/9/2014 8:32:30 AM | A | PASS |
|
|
Call for lock box code if no one is there Phone #: ###-#### Inspection requested via web by robert feller Wall rough in ok cover
|