Inspections for the day of: Tuesday, December 9, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01079 ELE-Aging Inspection12/9/201412/9/201412/9/2014 3:29:42 PM DONE
still under construction
ELE14-03219 Electrical Rough-In12/9/201412/9/201412/9/2014 2:44:09 PMPPASS
Underslab electrical. Contact is Justin Bieker. Phone #: ###-#### Inspection requested via web by Richard Montgomery ok cover u/g ne part slab anop
ELE14-01816 Conference12/9/201412/9/201412/9/2014 2:20:52 PMPDONE
Skilled Nursing building "J" conference on Spa room J108. Call Lonny when on-site. Phone #: ###-#### Inspection requested via web by Lonny Baum talked about and looked at spa area, wrote correction notice,NEC 680.43(A) receptacles shall be at least 6' from inside walls of spa, and be gfci protected, 680.43(B) luminaires shall be gfci protected if less than 7'-6" from spa, shall have glass or plastic globe and be suitable for use in a damp location, 680.43(C) switches shall be at least 5' from inside walls of spa
ELE14-01814 Electrical Rough-In12/9/201412/9/201412/9/2014 1:51:23 PMPPASS
Rough-in ceiling inspection IL building area "E" 2nd floor corridor E251 ; 3rd floor corridor E351. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ok cover upper level ceiling as requested
ELE14-01812 Electrical Rough-In12/9/201412/9/201412/9/2014 1:18:30 PMPPASS
Rough-in ceiling soffit inspection for IL 2nd floor area "B" rooms: B200, B201, B202, B203, B204, B205, B206, B207, ; B209. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum ceiling soffits ok cover as requested
ELE14-03384 Rough-In Permanent Service12/9/201412/9/201412/9/2014 12:25:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
ELE14-03265 Final12/8/201412/9/201412/9/2014 10:34:29 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan ok final
ELE14-03095 Final12/8/201412/9/201412/9/2014 9:55:28 AMAPASS
David Phone #: ###-#### ok final
ELE14-03142 Electrical Rough-In12/8/201412/9/201412/9/2014 9:23:49 AMAPASS
Wall Cover. Toby is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen walls and ceilings ok cover
ELE14-03056 Final12/8/201412/9/201412/9/2014 8:43:05 AMAFAIL
Jay// space 5 Phone #: ###-#### called, left message, NEC 210.8(B)(2) all receptacles in kitchen shall be gfci, 406.(D) receptacle faceplates shall be flush with or project from receptacle, BCC shall not cover ceiling prior to inspection, receptacles shall operate, complete panel schedule, provide light switches for dining area and identify, strap mc cable within 12" of box, verify convenience receptacle within 25' of rooftop units