Inspections for the day of: Wednesday, December 9, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01786 ELE-Aging Inspection12/9/201512/9/201512/10/2015 9:21:16 AM DONE
too busy
GCE15-00151 GCE-Final12/9/201512/9/201512/10/2015 8:36:30 AMPPASS
Terry ###-#### code: 3484 final ok
GCE15-00151 GCE-Final12/9/201512/9/201512/9/2015 3:59:34 PMPPASS
Terry ###-#### final ok
GCE15-00171 GCE-Rough-In12/9/201512/9/201512/9/2015 3:02:16 PMPFAIL
Greg ###-#### 210.52(G)(1)- the branch circuit supplying garage receptacles shall not supply outlets outside of the garage. metal boxes shall be grounded at rough in stage 320.23(A)- cables run within 6 foot of attic crawl shall be protected with gaurd strips. remove all drywall covering full length of nm cable not yet inspected
GCE15-00112 GCE-Permanent Service12/9/201512/9/201512/9/2015 2:14:12 PMPFAIL
Bob ###-#### still need fire sprinkeler riser bonded and available fault current info label
GCE15-00112 GCE-Rough-In12/9/201512/9/201512/9/2015 2:11:54 PMPPASS
Bob ###-#### r/i walls ok upst. offices and corridor see sheet A2.1 pink highlighted areas
ELE15-03695 Electrical Rough-In12/9/201512/9/201512/9/2015 1:09:48 PMPPASS
Walls only inspection Phone #: ###-#### Inspection requested via web by Nick Larson r/i ok walls
ELE15-02918 Final12/8/201512/9/201512/9/2015 12:44:10 PMPPASS
ARC FAULT Breakers were installed. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld corrections made final ok
ELE15-03769 Final12/8/201512/9/201512/9/2015 10:39:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by Todd Sellman as per manufacturer- 50 amp maximum on top position of all in one. Relocate 80 amp breaker and turn on 200 amp main. 250 .94- intersystem bus bar required
ELE15-02606 Final12/8/201512/9/201512/9/2015 9:54:05 AMAPASS
Please call Mitch at ###-#### 30 minutes before. Phone #: ###-#### Inspection requested via web by Mitch Whited correction made final ok
ELE15-02604 Final12/8/201512/9/201512/9/2015 9:37:48 AMAPASS
Jake is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates corrections made final ok perm. occupancy ok
ELE15-03525 Electrical Rough-In12/8/201512/9/201512/9/2015 9:08:54 AMAPASS
Luke on site. Phone #: ###-#### Inspection requested via web by Clint Tate r/i ok both bathroom ceilings, POS counters and lobby wall opposite POS area
ELE15-02903 Final12/9/201512/9/201512/9/2015 8:50:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder final ok