ELE13-00268
| ELE-Aging Inspection | 12/9/2015 | 12/9/2015 | 12/10/2015 6:22:06 AM | | CANC |
|
|
too busy
|
ELE11-01079
| ELE-Aging Inspection | 12/9/2015 | 12/9/2015 | 12/10/2015 6:21:15 AM | | CANC |
|
|
too busy
|
ELE15-03895
| Rough-In Permanent Service | 12/9/2015 | 12/9/2015 | 12/9/2015 1:52:11 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE15-02920
| Final | 12/9/2015 | 12/9/2015 | 12/9/2015 1:09:36 PM | P | NR |
|
|
Inspection requested via web by Krista Ratterree called, painters shall allow access to panel, garage gfci shall operate, shall install globe on closet light upstairs
|
ELE15-02585
| Final | 12/9/2015 | 12/9/2015 | 12/9/2015 12:36:23 PM | P | PASS |
|
|
Darren-please call for access Phone #: ###-#### called office, they said ok for inspection, ok final
|
ELE14-01066
| Electrical Rough-In | 12/8/2015 | 12/9/2015 | 12/9/2015 11:31:24 AM | A | CANC |
|
|
Partial Final H building, second floor final. Contact Craig Timmons. Phone #: ###-#### Inspection requested via web by Cathy Duchek see part final
|
ELE14-01066
| Final | 12/9/2015 | 12/9/2015 | 12/9/2015 11:29:40 AM | A | PART |
|
|
Partial Final H building, second floor final. Contact Craig Timmons. Phone #: ###-#### Inspection requested via web by Cathy Duchek ok part final, 3rd floor
|
ELE15-03861
| Final | 12/8/2015 | 12/9/2015 | 12/9/2015 9:25:39 AM | A | PASS |
|
|
Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan ok final
|
ELE15-03951
| Rough-In Permanent Service | 12/8/2015 | 12/9/2015 | 12/9/2015 9:17:32 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe called, left correction notice, NEC 334.23 shall protect nm cable within 6' of attic access, 300.4(A),(D) shall protect nm cable withun 1 1/4" of edge of bored hole and face of framing member, 334.39 shall not staple nm on edge, 210.52(G) shall not supply outside receptacle outside of car space, 210.17 shall supply electric vehicle branch circuit
|
ELE15-03861
| Permanent Service | 12/8/2015 | 12/9/2015 | 12/9/2015 8:43:02 AM | A | PASS |
|
|
Thanks! Phone #: ###-#### Inspection requested via web by Clay Morgan p/s u/g rec ok
|
ELE15-03861
| Electrical Rough-In | 12/8/2015 | 12/9/2015 | 12/9/2015 8:03:45 AM | A | PASS |
|
|
Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan ri ok
|