BLD15-03286
| BLD-Final | 12/9/2015 | 12/9/2015 | 12/10/2015 8:16:00 AM | P | NR |
|
|
Due to a secondary slab that averaged 15" thick under the top slab, footings were no longer needed and columns were bolted down. We have documentation on site. Phone #: ###-#### Inspection requested via web by Darius Saxton
|
BLD15-04079
| BLD-Framing/Rough-in | 12/8/2015 | 12/9/2015 | 12/9/2015 3:20:39 PM | P | PASS |
|
|
Bob Phone #: ###-####. Interior steel stud framed walls for new offices and breakroom only ok.
|
BLD15-02561
| BLD-Framing/Rough-in | 12/8/2015 | 12/9/2015 | 12/9/2015 3:09:16 PM | P | FAIL |
|
|
Kelly Phone #: ###-####. Provide fix ffrom joist manufacturer for cut top chords on floor joist in unit 102. Fire caulk in riser room, Complete draft stop in attic above tub, unit 104. Correction notice posted, ok to insulate.
|
BLD15-00723
| BLD-Ceiling Grid Inspection | 12/9/2015 | 12/9/2015 | 12/9/2015 2:25:00 PM | P | PASS |
|
|
Brent Phone #: ###-####. East offices only ok.
|
BLD15-01213
| BLD-Foundation | 12/9/2015 | 12/9/2015 | 12/9/2015 1:30:41 PM | P | PART |
|
|
Rebar // Dave Phone #: ###-####. No plans or new engineering on site. Per Bob Archibald, allowed concrete to be placed, but engineering will be required prior to final inspection. Footings were approx. 4ft.x4ft. 34inches to 42 inches deep with two mats of 4#5 rebar each way.
|
BLD15-04082
| BLD-Final | 12/8/2015 | 12/9/2015 | 12/9/2015 1:26:49 PM | P | PASS |
|
|
Gari-please call 30 minutes prior for access Phone #: ###-####
|
BLD15-04082
| DOC - Permit Finaled | 12/9/2015 | 12/9/2015 | 12/9/2015 1:25:59 PM | P | PASS |
|
|
|
BLD15-03903
| BLD-Foundation | 12/8/2015 | 12/9/2015 | 12/9/2015 11:24:43 AM | P | PART |
|
|
Dame Phone #: ###-####
|
BLD15-04181
| BLD-Footing | 12/8/2015 | 12/9/2015 | 12/9/2015 11:12:36 AM | A | PASS |
|
|
would like call ahead; Warren Phone #: ###-####
|