Inspections for the day of: Monday, December 9, 2019.
Number of inspections: 25
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05533 Final12/6/201912/9/201912/9/2019 3:46:23 PMPPART
PLEASE CALL MY LEAD INSTALLER HARLEY WHEN 30-40 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- partial final need to see an electrical permit by others
MEC19-05533 Pressure Test12/6/201912/9/201912/9/2019 3:45:37 PMPPASS
PLEASE CALL MY LEAD INSTALLER HARLEY WHEN 30-40 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- 20lb gas pressure test
- tagged gas line
MEC19-04828 Rough-in12/7/201912/9/201912/9/2019 3:02:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Michael Stimpson
- R/I ok
MEC19-05364 Final12/9/201912/9/201912/9/2019 2:38:40 PMPFAIL
PLEASE CALL HOMEOWNER CRAIG WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
- need to witness 5lb flue test
MEC19-01757 Final12/9/201912/9/201912/9/2019 2:09:29 PMPPASS
final ok occ card signed
MEC19-04691 Final12/9/201912/9/201912/9/2019 2:09:07 PMPPASS
UV protection for refrigeration lines completed - ready to inspect Phone #: ###-#### Inspection requested via web by Clay Bonvillain
- final ok occ card signed
MEC19-05509 Pressure Test12/9/201912/9/201912/9/2019 1:59:44 PMPPASS
10 mil tape is complete. Phone #: ###-#### Inspection requested via web by Scott Sparrell
- will final permit when flex connection is installed to meter bar
MEC19-02873 Final12/6/201912/9/201912/9/2019 1:40:38 PMPFAIL
Please call prior to arrival if possible, Kaye Flet at ###-####. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- A/C needs locking caps installed on service ports
- new line set is within 1" of b vent through attic
MEC19-04013 Final12/8/201912/9/201912/9/2019 1:17:56 PMPPASS
call josh 20 min ahead please Phone #: ###-#### Inspection requested via web by Manuel Canto
- final ok
MEC19-04627 Final12/9/201912/9/201912/9/2019 12:57:31 PMPPASS
Please call me an hour before inspection. I would like to be there with you for final inspection. ###-#### Phone #: ###-#### Inspection requested via web by Terry Warden
- final ok
MEC19-05121 Pressure Test12/9/201912/9/201912/9/2019 12:35:40 PMPPASS
Entrance code: 8098
Gas line leak repaired. Phone #: ###-#### Inspection requested via web by Nicolas Barajas
- 20lb gas pressure test ok
- tagged meter location
MEC19-05121 Rough-in12/9/201912/9/201912/9/2019 12:35:15 PMPPASS
Entrance Code: 8098
Gas line leak repaired. Phone #: ###-#### Inspection requested via web by Nicolas Barajas
- R/I ok
MEC19-04003 Final12/9/201912/9/201912/9/2019 11:49:38 AMPPASS
ReInspect Phone #: ###-#### Inspection requested via web by Randy Hart
- final ok
MEC19-04004 Final12/9/201912/9/201912/9/2019 11:49:26 AMPPASS
Reinspect Phone #: ###-#### Inspection requested via web by Randy Hart
- final ok
MEC19-04658 Rough-in12/4/201912/9/201912/9/2019 11:49:11 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- one supply boot in garage needs insulated
- approved manJ onsite
MEC19-04658 Pressure Test12/4/201912/9/201912/9/2019 11:48:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb gas pressure test ok
- tagged meter location
MEC19-04002 Final12/4/201912/9/201912/9/2019 11:48:09 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- final ok
MEC19-05382 Rough-in12/6/201912/9/201912/9/2019 11:03:33 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- no access to inspect 2nd floor fireplace vent
MEC19-02964 Pressure Test12/6/201912/9/201912/9/2019 10:39:13 AMAFAIL
Pressure test on gas above laundry room for water heater. call 30 mins before arriving. Phone #: ###-#### Inspection requested via web by adrian manzo
- need stamped set of prints onsite
MEC19-05486 Final12/6/201912/9/201912/9/2019 9:49:32 AMAFAIL
Inspection requested via web by Jeff Glynn
- line set near A/C needs supported
- A/C needs locking caps installed on service ports
MEC19-03593 Final12/6/201912/9/201912/9/2019 9:26:28 AMAFAIL
LOCK BOX 7432 Phone #: ###-#### Inspection requested via web by Aaron Alandt
- need to see Duct Blast test
- line set in wall of laundry room needs insulation re installed
- gas line penetration needs sealed
MEC19-04645 Rough-in12/6/201912/9/201912/9/2019 8:54:30 AMACANC
Garage code is 0880, house is vacant, manual J is on wall where furnace will be. Please call with any questions Phone #: ###-#### Inspection requested via web by Gary Duncan
- scheduled wrong permit this project is not ready for final yet per Gary Ducan
MEC19-05515 Rough-in12/7/201912/9/201912/9/2019 8:41:32 AMAFAIL
Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- insulation shield on b vent in attic
- install transfer air openings into front bedrooms
- finish remaining gas piping and re test for meter tag
MEC19-00390 Mec-Aging Inspection12/9/201912/9/201912/9/2019 8:06:39 AM PASS
Doc Permit Expired ok
MEC19-00390 DOC - Permit Expired12/9/201912/9/201912/9/2019 8:06:03 AMAPASS
Doc Permit Expired ok permit not active