ELE06-00066
| Electrical Rough-In | 2/1/2006 | 2/1/2006 | 2/1/2006 4:43:31 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 2/1/2006 at 9:16:00 AM. Contact: ###-####. r/i ok
|
ELE06-00374
| Final | 2/1/2006 | 2/1/2006 | 2/1/2006 3:42:58 PM | P | PASS |
|
|
PLEASE DO FINAL INSPECTION. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
|
ELE06-00058
| Electrical Rough-In | 2/1/2006 | 2/1/2006 | 2/1/2006 3:15:47 PM | P | PART |
|
|
u/g ok rental car area, layton trailer area, planters around parking structure ok
|
ELE06-00329
| Electrical Rough-In | 2/1/2006 | 2/1/2006 | 2/1/2006 2:09:17 PM | P | FAIL |
|
|
energy code compliance being changed by engineer will provide as soon as possible; Phone #: ###-#### Internet Inspection Request from: joe corrections not made 1 more created 300.11(C) shall not use cable to secure or support other cables, 330.30 secure cables within 12' of boxes, 300.4 nail pltes and 11/4" inside outside edges of framing members, had Mike Kinnear look at job also Mike found the same violations called
|
ELE05-03919
| Final | 2/1/2006 | 2/1/2006 | 2/1/2006 1:00:40 PM | P | NR |
|
|
REINSPECTION OF SERVICE; Phone #: ###-#### Internet Inspection Request from: Randy Vail no final conference ok only when ready needs to call for p/s not final
|
ELE05-02848
| Final | 2/1/2006 | 2/1/2006 | 2/1/2006 12:13:16 PM | P | PASS |
|
|
butch --re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok shell and core no card
|
ELE06-00367
| Rough-In Permanent Service | 1/31/2006 | 2/1/2006 | 2/1/2006 10:13:21 AM | A | PASS |
|
|
Gene ###-#### r/i ok still needs r/i for din and kit area p/s o/h rec. ok
|
ELE06-00329
| Electrical Rough-In | 1/31/2006 | 2/1/2006 | 2/1/2006 9:37:17 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler cor. do not cover posted called 300.4 nail plates & 11/4" 330.30 strap MC within 12" of boxes energy code lighting ? had contractor call BLD inspector
|
ELE06-00362
| Conference | 1/31/2006 | 2/1/2006 | 2/1/2006 8:38:39 AM | A | DONE |
|
|
###-#### - mirela ok
|
ELE06-00365
| Electrical Rough-In | 1/31/2006 | 2/1/2006 | 2/1/2006 8:04:48 AM | A | PART |
|
|
###-#### electrode ok
|
ELE06-00374
| Permanent Service | 2/1/2006 | 2/1/2006 | 2/1/2006 12:00:00 AM | P | PASS |
|
|
PLEASE DO FINAL INSPECTION. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g new ok
|
ELE06-00364
| Electrical Rough-In | 1/31/2006 | 2/1/2006 | 1/31/2006 4:52:04 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
ELE05-03110
| Final | 1/31/2006 | 2/1/2006 | 1/31/2006 12:59:44 PM | A | PASS |
|
|
Roger -- rescheduled insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
|