Inspections for the day of: Wednesday, February 1, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02178 FIRE-Final Inspection2/1/20062/1/20062/1/2006 6:58:43 PMPFAIL
Door closures at some locations need adjustment, smoke detectors must meet the requirements of NFPA 72 2002 11.8.3.1 and 11.8.3.5 with respect to location, fire dept. access and building addressing are acceptable.
BLD05-01630 FIRE-Final Inspection2/1/20062/1/20062/1/2006 6:52:27 PMPCANC
No fire inspection related to or required for this project, notified the contractor to request a structural inspection.
BLD02-02177 FIRE-Final Inspection2/1/20062/1/20062/1/2006 3:30:11 PMPFAIL
Door closures at some locations need to be adjusted, smoke detectors must meet the requirements of NFPA 72 2002 11.8.3.1 and 11.8.3.5 with respect to location, fire dept. access and building addressing are acceptable.
FIR05-00458 INSP-Final Inspection2/1/20062/1/20062/1/2006 2:25:21 PMPPASS
UG fire supply permit finaled.
FIR05-00542 INSP-Sprinkler Rough-in1/31/20062/1/20062/1/2006 11:00:45 AMAFAIL
One head in the mechanical room is blocked by close proximity to a unistrut support, the hose stations are not installed at this time, heads on the branch lines at exterior covered canopies need minor adjustment with respect to the deflector orientation and pitch of roof, the FDC is poorly located (partially obstructed by adjacent stairs, handrails, and door when in the open position) see review notes for comments and NFPA 13 8.16.2.4.6, IFC 508.5.4, IFC 903.3.7 for requirements.
FIR05-00458 INSP-Supply line flush1/31/20062/1/20062/1/2006 10:49:55 AMAPART
UG fire supply line flush is satisfactory.