Inspections for the day of: Thursday, February 1, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04068 ELE-Aging Inspection2/1/20072/1/20072/1/2007 3:15:49 PMPDONE
talked with contractor still waiting for response
ELE07-00359 Permanent Service2/1/20072/1/20072/1/2007 2:48:00 PMPFAIL
alan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
no correction posted called need access to inside of house, noted to contr. B C C no violations to be retained, use manufactures listed breakers only, shall not ID 6 or smaller neutral told contr to check p/s out and wire to 2005 NEC
ELE06-03350 Final2/1/20072/1/20072/1/2007 1:54:55 PMPPASS
Thank you - On site journeyman Randy ###-####.
Phone #: ###-#### ok corrections made, closet fixtures clearence ok
ELE07-00362 Rough-In Permanent Service2/1/20072/1/20072/1/2007 1:35:34 PMPPASS
Scheduled by a contractor via Hello! on 2/1/2007 at 10:01:34 AM. Contact: ###-####. p/s u/g for new meter ok
ELE07-00094 Final2/1/20072/1/20072/1/2007 12:59:12 PMPNR
Phone #: ###-#### called contr requested inspection by mistake job not ready
ELE06-04355 Final2/1/20072/1/20072/1/2007 12:57:56 PMPPASS
Phone #: ###-#### ok shell and core only card signed
ELE06-04586 Final2/1/20072/1/20072/1/2007 12:57:16 PMPFAIL
Phone #: ###-#### corrr. called 110.26(A)(1) table shall provide required clearences for panels, 406.4(A B D) recepts are loose in boxes and set back in plates, all locations
ELE07-00277 Electrical Rough-In1/31/20072/1/20072/1/2007 11:09:15 AMAPASS
jason - the painter will let you; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok added final ok
ELE07-00277 Final2/1/20072/1/20072/1/2007 11:08:37 AMAPASS
jason - the painter will let you; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
ELE07-00103 Final1/31/20072/1/20072/1/2007 10:55:21 AMAFAIL
lewis; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
corr. fee due called 310.15(B)(2)(a) derate conductors from p/s to jbox (old panel)
ELE06-04035 Final1/31/20072/1/20072/1/2007 10:27:33 AMAFAIL
garage code 2690 Phone #: 208-371-641
corr. corr. called 314.16 box fill island counter
ELE06-02125 Final1/31/20072/1/20072/1/2007 9:53:05 AMAFAIL
Monument sign for Designs West Phone #: ###-#### corr. called 314.17 fitting required for all raceways that enter sign, 300.15 all splices shall be in box or enclosure, 314.23 support boxes if used, 300.12 mech continunity of raceways, 350.6, 352.6 shall use listed fttings for LFMC &RNC
ELE06-04523 Final1/31/20072/1/20072/1/2007 9:20:44 AMACANC
This is the C & C cleaners on State. Phone #: ###-#### called need correct address should be 5622 w state
ELE06-04337 Final1/31/20072/1/20072/1/2007 8:42:21 AMAPASS
kelly; Phone #: ###-#### Internet Inspection Request from: Victoria
ok flex fittings removed final ok