BLD06-02716
| FIRE-Final Inspection | 2/1/2007 | 2/1/2007 | 2/2/2007 12:12:35 PM | P | FAIL |
|
|
Need to repair the two exit signs at hall 227 which are not functional on battery backup.
|
FIR06-00596
| INSP-Alarm Testing | 1/31/2007 | 2/1/2007 | 2/1/2007 9:15:13 PM | P | PART |
|
|
Need to retest elevator recall functions, the manual pull stations at the first floor lobby are installed above max. allowable height AFF, the tamper switch at the OS&Y @ tank suction is not functional, need to provide an additional module for the tank fill level monitoring, provide current as-builts and map at the panel, covers at SD shall be removed prior to final permit approval.
|
FIR06-00294
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 9:09:31 PM | P | PASS |
|
|
Per field inspection completed by B. Johnson, the fire sprinkler installation is satisfactory. Noted several locations at tenant spaces where storage heights and housekeeping procedures are not code compliant.
|
FIR06-00352
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 9:06:35 PM | P | PASS |
|
|
Per field inspection by B. Johnson, the fire sprinkler installation is satisfactory. Noted several areas at tenant spaces where storage heights exceed the maximum allowable.
|
FIR06-00449
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 9:01:09 PM | P | FAIL |
|
|
Per field inspection by B. Johnson, items needed for final include missing ceiling tiles, hard lids at canopy, fireproofing at the riser room.
|
FIR06-00945
| INSP-Sprinkler Rough-in/Hydro | 1/31/2007 | 2/1/2007 | 2/1/2007 8:58:12 PM | P | PART |
|
|
Per field inspection by B. Johnson, the overhead fire sprinkler rough-in including the booster pump and holding tank are acceptable.
|
FIR07-00057
| INSP-Sprinkler Rough-in | 1/31/2007 | 2/1/2007 | 2/1/2007 8:55:20 PM | A | PART |
|
|
Per field inspection completed by B. Johnson, the OH sprinkler rough-in is okay for cover.
|
FIR06-00890
| INSP-Sprinkler Rough-in | 1/31/2007 | 2/1/2007 | 2/1/2007 8:53:35 PM | A | PART |
|
|
Per field inspection by B. Johnson, OH rough-in is approved for cover.
|
FIR06-00728
| INSP-Sprinkler Rough-in | 1/31/2007 | 2/1/2007 | 2/1/2007 2:29:24 PM | A | FAIL |
|
|
Per field inspection completed by B. Johnson, upright heads at several locations are obstructed by ductwork.
|
FIR06-00997
| INSP-Final Inspection | 2/1/2007 | 2/1/2007 | 2/1/2007 2:26:18 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
BLD06-03046
| FIRE-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 1:10:23 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR07-00013
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 1:09:38 PM | A | PASS |
|
|
Fire sprinkler permit finaled, corrections verified.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 1/31/2007 | 2/1/2007 | 2/1/2007 1:08:57 PM | A | PART |
|
|
Air test for the 4th floor dry system passed with a max. allowable drop of 1 1/2 psi. over 24 hrs. Noted two locations with wet ceiling tile at the head.
|
FIR06-00762
| INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 2/1/2007 | 2/1/2007 1:07:12 PM | A | PART |
|
|
OH hydrostatic test for the second floor area 7 remodel completed acceptable, also approved the remainder of heads at the drop ceilings for cover.
|
FIR06-00997
| INSP-Alarm Testing | 1/31/2007 | 2/1/2007 | 2/1/2007 8:50:51 AM | A | PASS |
|
|
Fire alarm tested satisfactory, noted H/S in the short hallway exceed the max. dB level allowed, requested contractor to replace one device with a strobe only at this location.
|
FIR06-01018
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 2/1/2007 8:47:53 AM | A | PASS |
|
|
Final fire sprinkler field inspeciton passed, noted one missing escutcheon at the conference room to be installed today per Jim of TV and prior to bld final.
|
FIR06-00755
| INSP-Sprinkler Rough-in/Hydro | 1/31/2007 | 2/1/2007 | 2/1/2007 8:42:37 AM | A | NR |
|
|
Per phone call from the subcontractor, system is not ready for hydro at this time, to be rescheduled.
|
FIR06-00762
| INSP-Final Inspection | 1/30/2007 | 2/1/2007 | 2/1/2007 12:00:00 AM | A | CANC |
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
FIR05-00772
| INSP-Final Inspection | 1/31/2007 | 2/1/2007 | 1/31/2007 2:55:36 PM | A | FAIL |
|
|
Need to adjust the tamper switch at the PIV, provide pendent heads in the head box, attatch "911" sign at the outside bell, dry system #2 exceeds allowable trip time per NFPA for the system size (water was delivered to the test connection at 1min. 30 sec.).
|