Inspections for the day of: Thursday, February 1, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02716 FIRE-Final Inspection2/1/20072/1/20072/2/2007 12:12:35 PMPFAIL
Need to repair the two exit signs at hall 227 which are not functional on battery backup.
FIR06-00596 INSP-Alarm Testing1/31/20072/1/20072/1/2007 9:15:13 PMPPART
Need to retest elevator recall functions, the manual pull stations at the first floor lobby are installed above max. allowable height AFF, the tamper switch at the OS&Y @ tank suction is not functional, need to provide an additional module for the tank fill level monitoring, provide current as-builts and map at the panel, covers at SD shall be removed prior to final permit approval.
FIR06-00294 INSP-Final Inspection1/31/20072/1/20072/1/2007 9:09:31 PMPPASS
Per field inspection completed by B. Johnson, the fire sprinkler installation is satisfactory. Noted several locations at tenant spaces where storage heights and housekeeping procedures are not code compliant.
FIR06-00352 INSP-Final Inspection1/31/20072/1/20072/1/2007 9:06:35 PMPPASS
Per field inspection by B. Johnson, the fire sprinkler installation is satisfactory. Noted several areas at tenant spaces where storage heights exceed the maximum allowable.
FIR06-00449 INSP-Final Inspection1/31/20072/1/20072/1/2007 9:01:09 PMPFAIL
Per field inspection by B. Johnson, items needed for final include missing ceiling tiles, hard lids at canopy, fireproofing at the riser room.
FIR06-00945 INSP-Sprinkler Rough-in/Hydro1/31/20072/1/20072/1/2007 8:58:12 PMPPART
Per field inspection by B. Johnson, the overhead fire sprinkler rough-in including the booster pump and holding tank are acceptable.
FIR07-00057 INSP-Sprinkler Rough-in1/31/20072/1/20072/1/2007 8:55:20 PMAPART
Per field inspection completed by B. Johnson, the OH sprinkler rough-in is okay for cover.
FIR06-00890 INSP-Sprinkler Rough-in1/31/20072/1/20072/1/2007 8:53:35 PMAPART
Per field inspection by B. Johnson, OH rough-in is approved for cover.
FIR06-00728 INSP-Sprinkler Rough-in1/31/20072/1/20072/1/2007 2:29:24 PMAFAIL
Per field inspection completed by B. Johnson, upright heads at several locations are obstructed by ductwork.
FIR06-00997 INSP-Final Inspection2/1/20072/1/20072/1/2007 2:26:18 PMPPASS
Fire alarm permit finaled.
BLD06-03046 FIRE-Final Inspection1/31/20072/1/20072/1/2007 1:10:23 PMAPASS
Fire life safety inspection passed.
FIR07-00013 INSP-Final Inspection1/31/20072/1/20072/1/2007 1:09:38 PMAPASS
Fire sprinkler permit finaled, corrections verified.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro1/31/20072/1/20072/1/2007 1:08:57 PMAPART
Air test for the 4th floor dry system passed with a max. allowable drop of 1 1/2 psi. over 24 hrs. Noted two locations with wet ceiling tile at the head.
FIR06-00762 INSP-Sprinkler Rough-in/Hydro1/30/20072/1/20072/1/2007 1:07:12 PMAPART
OH hydrostatic test for the second floor area 7 remodel completed acceptable, also approved the remainder of heads at the drop ceilings for cover.
FIR06-00997 INSP-Alarm Testing1/31/20072/1/20072/1/2007 8:50:51 AMAPASS
Fire alarm tested satisfactory, noted H/S in the short hallway exceed the max. dB level allowed, requested contractor to replace one device with a strobe only at this location.
FIR06-01018 INSP-Final Inspection1/31/20072/1/20072/1/2007 8:47:53 AMAPASS
Final fire sprinkler field inspeciton passed, noted one missing escutcheon at the conference room to be installed today per Jim of TV and prior to bld final.
FIR06-00755 INSP-Sprinkler Rough-in/Hydro1/31/20072/1/20072/1/2007 8:42:37 AMANR
Per phone call from the subcontractor, system is not ready for hydro at this time, to be rescheduled.
FIR06-00762 INSP-Final Inspection1/30/20072/1/20072/1/2007 12:00:00 AMACANC
craig; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
FIR05-00772 INSP-Final Inspection1/31/20072/1/20071/31/2007 2:55:36 PMAFAIL
Need to adjust the tamper switch at the PIV, provide pendent heads in the head box, attatch "911" sign at the outside bell, dry system #2 exceeds allowable trip time per NFPA for the system size (water was delivered to the test connection at 1min. 30 sec.).