Inspections for the day of: Monday, February 1, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02116 ELE-Aging Inspection2/1/20162/1/20162/2/2016 9:03:48 AM CANC
too busy
ELE12-01425 ELE-Aging Inspection2/1/20162/1/20162/2/2016 9:03:12 AM CANC
too busy
ELE13-01958 ELE-Aging Inspection2/1/20162/1/20162/2/2016 9:02:13 AM CANC
too busy
ELE15-03544 Final2/1/20162/1/20162/1/2016 2:33:43 PMPFAIL
The owner will be on site Phone #: ###-#### Inspection requested via web by Craig Korell 210.8 (b) other then dwelling units all 120v 12@20 amp receptacles shall have GFCI protection 110.16 arc flash hazard sticker required
ELE15-03217 Final2/1/20162/1/20162/1/2016 1:47:17 PMPFAIL
John is on site Phone #: ###-#### Inspection requested via web by John Harvey 406.4 (5) tamper resistant receptaces required(master bath) 406.5 receptacle mounting shall be secured 406.9 receptacles intalled in a wet location shall be rated 422.31 permanently installed appliances shall a means of lock out trim out buried receptacles
ELE15-02819 Final2/1/20162/1/20162/1/2016 1:17:03 PMPPART
Phone #: ###-#### Inspection requested via web by kendall bender verify gfi protection in bath and w/r gfi in up balcony
ELE15-03552 Permanent Service1/29/20162/1/20162/1/2016 1:15:46 PMPCANC
Requesting wall rough-in AND service inspection. Phone #: ###-#### Inspection requested via web by Clint Tate needed r/i as well
ELE15-03552 Rough-In Permanent Service2/1/20162/1/20162/1/2016 1:14:59 PMPPASS
Requesting wall rough-in AND service inspection. Phone #: ###-#### Inspection requested via web by Clint Tate verify second ground source at detached house (needs 2 more ground rods) rough-in ok cover p/s o/h n ok
ELE15-03868 Final2/1/20162/1/20162/1/2016 12:45:35 PMPPASS
Call 15 to meet // Rocky Phone #: ###-#### final ok
ELE16-00256 Temporary Service1/29/20162/1/20162/1/2016 10:19:25 AMAPASS
Mark Phone #: ###-#### t/s o/h n ok
ELE16-00178 Final1/29/20162/1/20162/1/2016 9:57:54 AMAPASS
call first ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER service change final ok
ELE16-00148 Permanent Service2/1/20162/1/20162/1/2016 9:45:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder p/s u/g n ok
ELE16-00283 Final2/1/20162/1/20162/1/2016 9:29:09 AMPPASS
Tom Phone #: ###-#### final on time clocks ok
ELE16-00249 Rough-In Permanent Service1/29/20162/1/20162/1/2016 9:26:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson rough-in ok cover p/s u/g n ok
ELE16-00275 Final1/29/20162/1/20162/1/2016 8:57:02 AMAPASS
Contact: Jeremiah Goins Phone #: ###-#### Inspection requested via web by Deb Gooden final on jetted tub ok