FIR02-00459
| INSP-Conference | 2/10/2003 | 2/10/2003 | 2/10/2003 12:00:00 AM | P | PASS |
|
|
inspection was for the remaining underground supply line that needed covering. The piping from the man hole to the interior stub-in is ok to cover 2/10/2003 3:14:23 PM
|
BLD03-00007
| FIRE-Sprinkler Rough-in | 2/10/2003 | 2/10/2003 | 2/10/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 2/10/2003 at 8:05:28 AM. Contact: ###-####. 2/10/03-Troy called about this inspection, we think the GC entered the wrong inspection. I called GC and left mesg. that he would need to set up a new inspection or give me a call. lh
|
FIR02-00311
| INSP-Sprinkler Rough-in/Hydro | 2/10/2003 | 2/10/2003 | 2/10/2003 12:00:00 AM | P | PART |
|
|
###-#### jim The sprinkler piping in the plate room 222 on the second floor can be covered. One sprinkler head needs to be relocated and a hanger needs to be added. Locations are shown on the approved plans. The sprinkler pendants in the corridor outside of this room are overspaced and need corrected 2/10/2003 3:12:04 PM
|
BLD02-02701
| FIRE-Final Inspection | 2/10/2003 | 2/10/2003 | 2/10/2003 12:00:00 AM | P | FAIL |
|
|
JERRY- CELL ###-####- Areas in new tenant area lack fire sprinkler coverage. Provide approved fire sprinkler plans before performing work. Provide approved door hardware on interior doors per review note #12. Provide approved door hardware on front exit in vew space aor blank off the existing hardware and remove existing exit sign per Ron Hill ###-####. Provide approved door hardware on both rear exit doors. See review notes #6 and #12. Repair exit signs and test the emergency light. Provide fire extinguishers and tag the existing fire extinguishers. 2/10/2003 1:37:41 PM
|