Inspections for the day of: Tuesday, February 10, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00575 FIR-Aging Inspection2/10/20042/10/20042/10/2004 12:00:00 AM PASS
this project is still under construction 2/10/2004 12:47:59 PM
FIR03-00732 INSP-Final Inspection2/9/20042/10/20042/10/2004 12:00:00 AMAFAIL
8:30 strobe not installed per plans and the 75 cd strobe doesn't reach the south wall 2/10/2004 9:42:57 AM
FIR03-00601 INSP-Sprinkler Rough-in/Hydro2/9/20042/10/20042/10/2004 12:00:00 AMAPART
don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore okay to cover; need data on trapeeze's; need resubmittals for changes (upright heads used above grid throughout and minor changes to head layout in open multi - purpose room); still need hydro and alarm tests; vestibule not completed so branch line isn't installed yet 2/10/2004 4:03:43 PM
FIR04-00082 INSP-Sprinkler Rough-in/Hydro2/9/20042/10/20042/10/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/9/2004 at 5:09:14 PM. Contact: ###-####. UG okay to cover; sleeve needed for ductile; tamper conduit not installed yet; 2/10/2004 11:09:11 AM
FIR04-00017 INSP-Final Inspection2/10/20042/10/20042/10/2004 12:00:00 AMAPASS
BLD03-01977 FIRE-Conference2/10/20042/10/20042/10/2004 12:00:00 AMAPART
sprinklers heads not installed in all rooms in basement; heads obstructed in basement; need cages on all heads; curtain installed at main exit obstructing it and plastic lobby installed at main exit; repair exit sign; called GC ###-#### about these problems 2/10/2004 9:45:16 AM
BLD03-02937 FIRE-Final Inspection2/6/20042/10/20042/10/2004 12:00:00 AMAPASS
###-#### craig
FIR03-00115 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter. 1 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:55:09 PM 2/10/2004 3:56:31 PM
FIR03-00135 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter 2 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:55:22 PM 2/10/2004 3:56:14 PM
FIR03-00136 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter 3 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:55:55 PM
FIR03-00137 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter 4 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:57:11 PM
FIR03-00138 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter 5 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:57:27 PM
FIR03-00139 INSP-Sprinkler Rough-in/Hydro2/6/20042/10/20042/10/2004 12:00:00 AMAFAIL
Scott Carter 6 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:54:55 PM 2/10/2004 3:56:53 PM
FIR03-00642 INSP-Final Inspection2/9/20042/10/20042/10/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/9/2004 at 9:06:53 AM. Contact: ###-####.
BLD03-01636 FIRE-Final Inspection2/10/20042/10/20042/10/2004 12:00:00 AMPPASS
fire/life safety final okay 2/10/2004 4:00:01 PM